CEC Rule 8-102 in brief
The Canadian Electrical Code, Part I (CSA C22.1), Rule 8-102 says voltage drop in an installation must not exceed:
- 5% from the supply side of the consumer's service (or the secondary of the transformer for a separately derived system) to the point of utilization, and
- 3% in a feeder or branch circuit.
The demand load used is the connected load if known, or 80% of the overcurrent device rating. Because these are code requirements in Canada, inspectors can and do check them on long runs, especially detached garages, shops and outdoor equipment.
The formula
Single phase: VD = 2 × I × R × L ÷ 1000
Three phase: VD = 1.732 × I × R × L ÷ 1000
L in feet = L in metres × 3.28084
R is the conductor resistance in ohms per 1000 ft. For example, 10 AWG copper is 1.21 Ω and 8 AWG is 0.764 Ω. Full values are in the wire gauge chart.
Worked examples
1. Detached garage subpanel, 240 V
A 30 A load at 240 V, 40 m from the house, on 10 AWG copper:
L = 40 × 3.28084 = 131.2 ft
VD = 2 × 30 × 1.21 × 131.2 ÷ 1000 = 9.53 V → 3.97%
That is over the 3% branch circuit limit. 8 AWG copper gives 6.01 V, or 2.51%, which complies. If you don't know the load, the code basis is 80% of a 30 A breaker, 24 A, which gives 3.18% on 10 AWG, still over the limit.
2. 347 V lighting circuit
20 A on a 347 V lighting circuit, 60 m, 10 AWG copper:
L = 196.9 ft
VD = 2 × 20 × 1.21 × 196.9 ÷ 1000 = 9.53 V → 2.75%
Within 3%. Higher voltage makes 347 V lighting efficient over long distances in warehouses and parking structures.
3. 600 V feeder
150 A over 91 m (300 ft) on 3/0 aluminum, three phase: VD = 1.732 × 150 × 0.126 × 300 ÷ 1000 = 9.82 V, or 1.64% of 600 V. See the 3 phase voltage drop calculator for more feeder examples.
Fixing excessive voltage drop
- Upsize the conductors. Each two-gauge step cuts resistance by about 37%.
- Use a higher voltage: run a 240 V circuit instead of 120 V where the equipment allows.
- Move the panel or add a subpanel closer to the loads.
- Split the load across more circuits.
When you upsize for voltage drop, check whether the bonding conductor and conduit size need to change too. Check the raceway with the Canadian conduit fill calculator.
Ampacity in Canada
Voltage drop is only one check. Conductors must also meet CEC Table 2 (copper) or Table 4 (aluminum) ampacity, with the Rule 4-006 termination temperature limits and Rule 14-104 small-conductor protection limits (14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A). The wire size calculator applies the equivalent NEC values, which are close for common sizes.