Voltage Drop Calculator

Enter the wire size, load current, one-way length and voltage. You get the voltage drop in volts and percent, the voltage left at the load, and the smallest wire that keeps the drop under 3%.

—
Voltage drop—
Voltage at load—
Smallest size for ≤3%—

Resistance: NEC Chapter 9, Table 8 (75 °C, stranded, Ω/1000 ft). Limit:

How this voltage drop calculator works

Every conductor has resistance, so some of the source voltage is lost as heat along the run. The longer the wire, the higher the current and the smaller the conductor, the more voltage you lose. Too much drop makes motors run hot and stall, makes LED drivers flicker and makes heaters underperform. This calculator uses the same method most electricians and inspectors use in the field, with resistance values taken directly from NEC Chapter 9, Table 8.

The formula

Single phase: VD = 2 × I × R × L ÷ 1000
Three phase: VD = 1.732 × I × R × L ÷ 1000
VD% = VD ÷ source voltage × 100

Where I is the load current in amps, R is the conductor resistance in ohms per 1,000 feet, and L is the one-way length in feet. The factor 2 accounts for the out-and-back path on a single-phase circuit; 1.732 (√3) is used for a balanced three-phase circuit. For a deeper walkthrough, including the circular-mil (K-factor) version, see the voltage drop formula guide.

Worked example: 20 A circuit, 100 ft, 120 V

A 16 A load (80% of a 20 A circuit) is 100 feet from the panel on 12 AWG copper. Table 8 gives 1.93 Ω per 1,000 ft.

VD = 2 × 16 × 1.93 × 100 ÷ 1000 = 6.18 V
VD% = 6.18 ÷ 120 = 5.15%

That is well over the 3% recommendation. Moving to 10 AWG (1.21 Ω/kft) gives 3.87 V or 3.23%, still slightly over. 8 AWG (0.764 Ω/kft) gives 2.44 V or 2.04%, which passes. The calculator above reaches the same answer, and its "smallest size" box does the upsizing for you.

Worked example: aluminum feeder at 240 V

An 80 A subpanel feeder runs 150 ft on 2 AWG aluminum (0.319 Ω/kft) at 240 V single phase: VD = 2 × 80 × 0.319 × 150 ÷ 1000 = 7.66 V, or 3.19%. It is within the 5% total only if the branch circuits downstream add less than about 1.8%. Going to 1/0 aluminum brings the feeder to about 2%.

NEC and CEC voltage drop limits

In the US, the NEC treats voltage drop as a recommendation: informational notes to 210.19(A) (branch circuits) and 215.2 (feeders) suggest 3% for either and 5% total. Some sections are mandatory, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and energy codes may also limit drop. In Canada, CEC Rule 8-102 makes the limits a requirement: 3% on a feeder or branch circuit and 5% overall from the supply side of the consumer's service. Use our Canadian voltage drop calculator for metric lengths and 347/600 V systems.

Resistance values used (NEC Chapter 9, Table 8)

SizeCopper Ω/1000 ftAluminum Ω/1000 ft
14 AWG3.075.06
12 AWG1.933.18
10 AWG1.212
8 AWG0.7641.26
6 AWG0.4910.808
4 AWG0.3080.508
2 AWG0.1940.319
1/0 AWG0.1220.201

Values are DC resistance of uncoated stranded conductors at 75 °C. For large conductors on AC systems with a low power factor, reactance matters more; an engineer may use NEC Chapter 9 Table 9 effective impedance instead.

How to reduce voltage drop

Common mistakes

Entering the round-trip length (which doubles the answer), entering breaker size instead of load current, and forgetting that the 5% total includes the feeder and the branch circuit together. If you upsize ungrounded conductors for voltage drop, remember NEC 250.122(B) requires the equipment grounding conductor to be increased by the same proportion of circular mils. For three-phase feeders, use the 3 phase voltage drop calculator, and to size a conductor for both ampacity and drop at once, use the wire size calculator.

Frequently asked questions

What is an acceptable voltage drop?

The NEC recommends no more than 3% on a branch circuit or a feeder, and no more than 5% combined from the service to the farthest outlet. These are informational notes in 210.19(A) and 215.2, so they are recommendations unless your jurisdiction, an engineer, or equipment instructions make them mandatory. In Canada, CEC Rule 8-102 makes the 3% / 5% limits a requirement.

Do I use one-way or round-trip length?

Enter the one-way length from the source to the load. The calculator applies the factor 2 for single phase (current goes out and back) and √3 for balanced three phase.

Why does my result differ slightly from other calculators?

Calculators use different resistance data. This one uses NEC Chapter 9 Table 8 DC resistance at 75 °C for stranded conductors. Others use the K-factor method (K = 12.9 for copper) or Table 9 AC impedance with a power factor. Differences are usually a few tenths of a percent.

Is voltage drop the same for copper and aluminum?

No. Aluminum has about 1.6 times the resistance of copper of the same size, so it drops more voltage. That is why aluminum feeders are typically one or two sizes larger than copper for the same load.

Does voltage drop affect breaker size?

No. Breaker size is set by conductor ampacity and the load. Upsizing wire for voltage drop does not let you increase the breaker; the equipment grounding conductor must also be increased proportionally (NEC 250.122(B)).

What current should I enter?

Use the actual load current you expect to flow, not the breaker rating. For motors use the nameplate or table full-load current; for continuous loads use the real operating current (the 125% factor is for ampacity, not voltage drop).

Related calculators and charts