Wire Gauge Chart (AWG & kcmil)

Every building-wire size from 14 AWG to 1000 kcmil on one page: diameter, area, DC resistance and NEC ampacity for copper.

SizeDiameter (in)Diameter (mm)Area (cmil)Area (mm²)Cu Ω/1000 ftCu amps 60/75/90 °C
14 AWG0.06411.634,1102.083.0715 / 20 / 25
12 AWG0.08082.056,5303.311.9320 / 25 / 30
10 AWG0.10192.5910,3805.261.2130 / 35 / 40
8 AWG0.12853.2616,5108.370.76440 / 50 / 55
6 AWG0.16204.1226,24013.300.49155 / 65 / 75
4 AWG0.20435.1941,74021.150.30870 / 85 / 95
3 AWG0.22945.8352,62026.660.24585 / 100 / 115
2 AWG0.25766.5466,36033.620.19495 / 115 / 130
1 AWG0.28937.3583,69042.410.154110 / 130 / 145
1/0 AWG0.32498.25105,60053.510.122125 / 150 / 170
2/0 AWG0.36489.27133,10067.440.0967145 / 175 / 195
3/0 AWG0.409610.40167,80085.020.0766165 / 200 / 225
4/0 AWG0.460011.68211,600107.220.0608195 / 230 / 260
250 kcmil0.500012.70250,000126.670.0515215 / 255 / 290
300 kcmil0.547713.91300,000152.010.0429240 / 285 / 320
350 kcmil0.591615.03350,000177.340.0367260 / 310 / 350
400 kcmil0.632516.06400,000202.680.0321280 / 335 / 380
500 kcmil0.707117.96500,000253.350.0258320 / 380 / 430
600 kcmil0.774619.67600,000304.020.0214350 / 420 / 475
750 kcmil0.866022.00750,000380.030.0171400 / 475 / 535
1000 kcmil1.000025.401,000,000506.700.0129455 / 545 / 615

Diameter is bare solid conductor. Resistance is stranded uncoated copper at 75 °C from NEC Chapter 9 Table 8. Ampacity is NEC Table 310.16, before the 240.4(D) limits (14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A) and derating.

How the AWG scale works

American Wire Gauge is a logarithmic scale defined from two points: 36 AWG is 0.005 in and 0000 (4/0) is 0.46 in, with 38 equal ratio steps in between. The diameter of any gauge n is:

d (in) = 0.005 × 92(36 − n) ÷ 39

For 1/0 use n = 0, 2/0 is n = −1, 3/0 is n = −2 and 4/0 is n = −3. Area in circular mils is diameter in mils squared: a 0.1019 in (101.9 mil) 10 AWG conductor is 101.9² ≈ 10,380 cmil. Convert to mm² by multiplying by 0.0005067.

Rules of thumb

Example: comparing two sizes

Going from 12 AWG to 10 AWG raises area from 6,530 to 10,380 cmil, a 59% increase. Resistance falls from 1.93 to 1.21 Ω/kft, so voltage drop on the same run falls by 37%. On a 100 ft, 16 A, 120 V circuit that means 3.23% instead of 5.15%. Try it in the voltage drop calculator.

AWG vs metric sizes

Canada uses AWG for building wire, but most of the world sizes conductors in mm². Approximate equivalents: 14 AWG ≈ 2.08 mm² (next IEC size 2.5 mm²), 12 AWG ≈ 3.31 mm² (4 mm²), 10 AWG ≈ 5.26 mm² (6 mm²), 8 AWG ≈ 8.37 mm² (10 mm²), 6 AWG ≈ 13.3 mm² (16 mm²). Never substitute a smaller metric size for an AWG size.

Choosing a gauge

This chart is a reference. To choose a conductor, first check ampacity in the wire ampacity chart, apply any derating, then confirm voltage drop. The wire size calculator does all of this in one step, and the conduit fill calculator picks the raceway.

Gauge vs ampacity

A conductor's ampacity is not fixed by its size alone. It depends on insulation temperature rating, the terminal rating, ambient temperature, the number of current-carrying conductors bundled together, and whether it is in free air or a raceway. The 60/75/90 °C figures above are for not more than three current-carrying conductors in raceway or cable at 30 °C ambient.

Frequently asked questions

Why do smaller AWG numbers mean bigger wire?

AWG numbers come from the number of drawing steps used to make the wire. More passes through the dies made thinner wire, so 14 AWG is thinner than 10 AWG. After 1 AWG the scale continues 1/0, 2/0, 3/0, 4/0, then switches to kcmil.

What is kcmil?

Thousands of circular mils. One circular mil is the area of a circle 0.001 in in diameter. Sizes above 4/0 (211,600 cmil) are named by area: 250 kcmil, 500 kcmil and so on. You may also see MCM, the older name for the same unit.

How much does the diameter change between gauges?

Every 6 gauges halves the diameter; every 3 gauges roughly halves the cross-sectional area and doubles the resistance. 10 AWG has about twice the area of 13 AWG and four times that of 16 AWG.

Are these diameters for stranded or solid wire?

The diameters are for the bare solid conductor. Stranded conductors of the same gauge have the same area but are slightly larger in diameter. Insulated THHN is larger again; use the conduit fill calculator for insulated areas.

What gauge wire is used in house wiring?

14 AWG copper for 15 A lighting and receptacle circuits, 12 AWG for 20 A circuits (kitchens, bathrooms, laundry), 10 AWG for 30 A dryers and water heaters, and 8 or 6 AWG for ranges and EV chargers.