What Size Wire Do I Need for My Amps?

A quick chart for 15 A to 200 A circuits based on NEC Table 310.16, plus the rules that change the answer: terminal temperature, continuous loads, the small-conductor limits and voltage drop.

Wire size by amperage

Minimum conductor size for not more than three current-carrying conductors at 30 °C (86 °F) ambient.

CircuitCopper, 60 °C (NM cable)Copper, 75 °C (THHN, 75 °C terminals)Aluminum, 75 °C
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
90 A2 AWG3 AWG2 AWG
100 A1 AWG3 AWG1 AWG
125 A1/0 AWG1 AWG2/0 AWG
150 A3/0 AWG1/0 AWG3/0 AWG
200 A250 kcmil3/0 AWG250 kcmil

15, 20 and 30 A rows follow NEC 240.4(D): 14, 12 and 10 AWG copper are limited to 15, 20 and 30 A overcurrent protection no matter which column you use. Aluminum 12 and 10 AWG are limited to 15 and 25 A. Full values are in the wire ampacity chart.

Which temperature column applies?

Continuous loads: size for 125%

A load that runs three hours or more, such as an EV charger, water heater or lighting, needs conductors and overcurrent protection sized at 125% of the load (NEC 210.19(A) and 210.20(A)). A 40 A EV charger needs a 50 A circuit, so 6 AWG copper NM or 8 AWG THHN with 75 °C terminals.

Dwelling services and feeders: the 83% rule

For a 120/240 V single-phase dwelling service or main feeder, NEC 310.12 lets the conductor ampacity be 83% of the service rating. That is why 100 A services commonly use 4 AWG copper or 2 AWG aluminum, and 200 A services use 2/0 copper or 4/0 aluminum. It does not apply to branch circuits or to feeders that serve only part of the dwelling load.

Long runs: check voltage drop

The chart only covers heat. A 20 A, 120 V circuit on 12 AWG copper drops about 3% at 47 ft of one-way length with a full 20 A load. Past that, upsize. The voltage drop formula guide shows the math and the voltage drop calculator does it for you.

In Canada

CEC Tables 2 and 4 give the same ampacities for these sizes as NEC 310.16. Rule 8-102 makes the 3% and 5% voltage drop limits mandatory. See the Canadian voltage drop calculator.

This chart is a quick reference. Always confirm against the code edition your jurisdiction has adopted, the equipment markings and your inspector.

Frequently asked questions

What size wire for 30 amps?

10 AWG copper. NEC 240.4(D) limits 10 AWG copper to a 30 A overcurrent device, so 10 AWG is the minimum for a 30 A circuit. In aluminum, use 8 AWG.

What size wire for 50 amps?

6 AWG copper in NM cable (60 °C column, 55 A). With THHN in conduit and 75 °C rated terminals at both ends, 8 AWG copper (50 A) is allowed. In aluminum at 75 °C, use 6 AWG.

What size wire for 60 amps?

6 AWG copper at 75 °C (65 A) or 4 AWG copper at 60 °C (70 A). In aluminum at 75 °C, use 4 AWG (65 A).

What size wire for 100 amp service?

For a dwelling service, NEC 310.12 allows conductors rated at 83% of the service rating: 4 AWG copper or 2 AWG aluminum for 100 A. For a feeder or service that is not covered by 310.12, use the 75 °C column: 3 AWG copper or 1 AWG aluminum.

What size wire for 200 amp service?

Under NEC 310.12 for a dwelling: 2/0 copper or 4/0 aluminum. Outside 310.12, the 75 °C column needs 3/0 copper (200 A) or 250 kcmil aluminum (205 A).

Does wire length change the size?

Yes. Ampacity sets the minimum size, but on long runs voltage drop often requires a bigger conductor. Keep a branch circuit or feeder under about 3% drop. Use the wire size calculator, which checks both.