How box fill is calculated
NEC 314.16 limits how many conductors and devices go into a box so there's room to make up splices without damaging insulation or trapping heat. You count volume allowances under 314.16(B), multiply each by the volume for its wire size, and compare the total with the box volume.
| Item in the box | Allowances | Based on |
|---|---|---|
| Each insulated conductor that enters and is spliced, terminated or passes through | 1 each | That conductor's size |
| Each unbroken loop or coil 12 in (300 mm) or longer | 2 each | That conductor's size |
| Internal cable clamps (one or more) | 1 total | Largest conductor in the box |
| Fixture studs or hickeys | 1 per type | Largest conductor in the box |
| Each yoke or strap with one or more devices | 2 each | Largest conductor connected to the device |
| Equipment grounding conductors (one or more) | 1 total, +1 for an isolated ground set | Largest grounding conductor |
| Conductors that never leave the box (pigtails) | 0 | Not counted |
Required volume = Σ (allowances × Table 314.16(B) volume) ≤ box volume + marked ring volume
Volume per conductor (NEC Table 314.16(B))
| Conductor size | 18 AWG | 16 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
|---|---|---|---|---|---|---|---|
| Free space per conductor | 1.50 in³ | 1.75 in³ | 2.00 in³ | 2.25 in³ | 2.50 in³ | 3.00 in³ | 5.00 in³ |
Up to four fixture wires smaller than 14 AWG from a domed luminaire canopy, and a grounding conductor coming from such a canopy, can be left out of the count (314.16(B)(1) exception).
Worked examples
Switch fed by two 14/2 NM cables
Four insulated 14 AWG conductors = 4 × 2.00 = 8.00 in³. One switch = 2 × 2.00 = 4.00. Grounds = 2.00. Internal clamps = 2.00. Total 16.0 in³. That fits a 3 × 2 × 3-1/2 in device box (18.0 in³) but not a 3 × 2 × 2-1/2 in box (12.5 in³).
Receptacle with 12 AWG in a 4 in square box
Two 12/2 cables: 4 × 2.25 = 9.00 in³, plus the receptacle 4.50, grounds 2.25 and clamps 2.25 for 18.0 in³. A 4 × 1-1/2 in square box (21.0 in³) passes. Add a third 12/2 cable and it climbs to 22.5 in³, so step up to a 4 × 2-1/8 in square box (30.3 in³) or add a marked extension ring.
Ceiling light box with a fixture stud
Two 14/2 cables in a 4 × 1-1/2 in octagonal box (15.5 in³): conductors 8.00, grounds 2.00, fixture stud 2.00, clamps 2.00 for 14.0 in³. It fits. The luminaire's own fixture wires are not counted when they meet the exception above.
Maximum conductors in standard metal boxes
Box volumes are from NEC Table 314.16(A). Counts are box volume divided by the Table 314.16(B) allowance, for conductors of one size with nothing else in the box. Deduct allowances for devices, clamps, studs and grounds.
| Box | Volume | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
|---|---|---|---|---|---|---|
| 4 × 1-1/4 in round/octagonal | 12.5 in³ | 6 | 5 | 5 | 4 | 2 |
| 4 × 1-1/2 in round/octagonal | 15.5 in³ | 7 | 6 | 6 | 5 | 3 |
| 4 × 2-1/8 in round/octagonal | 21.5 in³ | 10 | 9 | 8 | 7 | 4 |
| 4 × 1-1/4 in square | 18 in³ | 9 | 8 | 7 | 6 | 3 |
| 4 × 1-1/2 in square | 21 in³ | 10 | 9 | 8 | 7 | 4 |
| 4 × 2-1/8 in square | 30.3 in³ | 15 | 13 | 12 | 10 | 6 |
| 4-11/16 × 1-1/4 in square | 25.5 in³ | 12 | 11 | 10 | 8 | 5 |
| 4-11/16 × 1-1/2 in square | 29.5 in³ | 14 | 13 | 11 | 9 | 5 |
| 4-11/16 × 2-1/8 in square | 42 in³ | 21 | 18 | 16 | 14 | 8 |
| 3 × 2 × 1-1/2 in device | 7.5 in³ | 3 | 3 | 3 | 2 | 1 |
| 3 × 2 × 2 in device | 10 in³ | 5 | 4 | 4 | 3 | 2 |
| 3 × 2 × 2-1/4 in device | 10.5 in³ | 5 | 4 | 4 | 3 | 2 |
| 3 × 2 × 2-1/2 in device | 12.5 in³ | 6 | 5 | 5 | 4 | 2 |
| 3 × 2 × 2-3/4 in device | 14 in³ | 7 | 6 | 5 | 4 | 2 |
| 3 × 2 × 3-1/2 in device | 18 in³ | 9 | 8 | 7 | 6 | 3 |
Tips from the field
- Plastic boxes are marked. Nonmetallic boxes and many metal boxes not listed in Table 314.16(A) carry their volume in cubic inches; use that number (314.16(A)(2)).
- Rings add volume. A plaster ring, mud ring or extension ring marked with its volume adds to the box. This is often the easiest fix for a box that's one allowance short.
- Large conductors use different rules. Boxes and conduit bodies with 4 AWG and larger conductors are sized under the pull and junction box rules in 314.28, not 314.16.
- GFCI and AFCI devices are deep. The code count doesn't change, but a deeper box makes them far easier to fold in.
- Working in Canada? Box fill falls under CEC Rule 12-3034 and its tables, which use a different method, so check those for CEC work.
Sizing the wire first? Use the wire size calculator or the wire size for amps chart. Pulling the same conductors in a raceway? Check the conduit fill calculator.