Box Fill Calculator (Canada, CEC)

Check an outlet, device or junction box against CEC Rule 12-3034. Enter the volume marked on the box in millilitres, your insulated conductors, marrettes and devices, and the calculator adds up the Table 22 space they need.

Insulated conductors that enter or leave the box, spliced, terminated or passing through. Don't count bare bonding conductors, pigtails that stay in the box, or No. 18/16 fixture wires of a luminaire mounted on the box.

—
Required space—
Usable box space—
Largest conductor—
Room left for more—

CEC Rule 12-3034 with Table 22 allowances. Connector, stud and device deductions use the largest conductor entered, the conservative case. Internal clamps take no allowance (Rule 12-3034(5)).

CEC data notice: CEC values were checked against public summaries of CSA C22.1:24, not the code book itself. Conduit and conductor areas use NEC Chapter 9 data, and some aluminum kcmil ampacities are unverified. Confirm against the CEC edition and provincial amendments adopted where you work.

How CEC Rule 12-3034 works

Rule 12-3034 of the Canadian Electrical Code, Part I (CSA C22.1:24) requires every box to have enough usable space for all the insulated conductors in it. It gives two ways to check:

  1. Table 23 (conductor count). For boxes of the nominal sizes listed in Table 23 where every conductor is the same size and no device is deeper than 2.54 cm, you can compare a conductor count with the table, after the deductions below (Subrule 2).
  2. Table 22 (volume). For any other box, any box with conductors of different sizes, or any box with a deep device, you add up the usable space each conductor needs from Table 22 and compare it with the box volume (Subrule 4).

The volume method works for every box, which is why this calculator uses it. Most boxes sold in Canada are marked with their volume in mL or cm³ (the two are the same unit). Only the space for conductors counts as filled, and the usable space is the box's internal volume (Subrule 5).

What counts and what doesn't

Item in the boxCounts asRule
Insulated conductor entering or leaving and connected to a terminal or connector1 conductor of its size12-3034(1)(b)
Insulated conductor passing through with no connection1 conductor of its size12-3034(1)(a)
Insulated conductor that never leaves the box (pigtail)012-3034(1)(c)
No. 18 or 16 fixture wires of a luminaire mounted on the box012-3034(1)(d)
Bare bonding conductors0 (only insulated conductors count)12-3034(1)
Each fixture stud or hickey1 conductor, largest size in the box12-3034(2)(a)
Every pair of wire connectors with insulating caps (marrettes)1 conductor, largest size under the connectors12-3034(2)(b)
Each flush-mounted device on a single strap2 conductors12-3034(2)(c)
Device deeper than 2.54 cm, strap to back32 cm³ × depth in cm12-3034(3)
Locknuts, bushings, box connectors, internal clamps012-3034(5)
Marked plaster ring, extension ring or raised coverAdds its marked volume to the box12-3034(6)

An insulated (green) bonding conductor is still an insulated conductor, and the rule text has no exception for it, so count it unless your inspector tells you otherwise.

Formula

Required space = Σ (conductors × Table 22 space) + deductions for studs, connector pairs and devices ≤ box volume + marked ring volume

Usable space per conductor (CEC Table 22)

Conductor sizemL (cm³)in³ equivalent
14 AWG24.61.50
12 AWG28.71.75
10 AWG36.92.25
8 AWG45.12.75
6 AWG73.74.50

These are smaller than the NEC Table 314.16(B) allowances (2.00 in³, or 32.8 mL, for 14 AWG), but the CEC adds space for marrettes and the NEC adds space for grounds and clamps, so the two codes can give different answers for the same box.

Worked examples

1. Switch loop in a 3 × 2 × 2-1/2 device box

A single-pole switch fed by one 14/2 NMD90 cable with a second 14/2 to the light: four insulated 14 AWG conductors, the bare bonds, one flush switch and three marrettes (bonds and neutrals). The box is 204 mL.

Conductors: 4 × 24.6 = 98.4 mL
Switch: 2 × 24.6 = 49.2 mL
Marrettes: 3 → 1 pair → 1 × 24.6 = 24.6 mL
Total = 172.2 mL ≤ 204 mL ✓

The bare bonding conductors add nothing. In conductor terms that is 7 against the 8 the box holds.

2. Replacing the switch with a smart switch

Same box, but the new switch measures 3.7 cm from strap to back. Subrule 3 applies, so the switch takes its own volume instead of two conductors:

Device: 32 × 3.7 = 118.4 mL
Total = 98.4 + 118.4 + 24.6 = 241.4 mL > 204 mL ✗

The box is overfilled. A 3 × 2 × 3 device box at 245 mL passes, at 99%. This is the scenario the Régie du bâtiment du Québec uses in its published interpretation of Rule 12-3034 (it rounds the factor to 32.3 cm³ per cm and gets 243 mL, with the same result).

3. Kitchen counter receptacle with three 12/2 cables

Feed in, two runs out: six insulated 12 AWG conductors, one receptacle, and three marrettes (hots with a pigtail, neutrals with a pigtail, bonds). The pigtails themselves never leave the box, so they don't count.

Conductors: 6 × 28.7 = 172.2 mL
Receptacle: 2 × 28.7 = 57.4 mL
Marrettes: 3 → 1 pair → 1 × 28.7 = 28.7 mL
Total = 258.3 mL

That doesn't fit a 245 mL device box. Use a box marked 258.3 mL or more, or a 4 in square box with a marked device ring so the combined volume is at least that. Add a fourth marrette and the connectors become two pairs, pushing the total to 287.0 mL, so plan the splices before you pick the box.

4. The same switch box under the NEC

Example 1 under NEC 314.16: four 14 AWG conductors, the switch (2), all grounds (1) and internal clamps (1) make 8 allowances × 2.00 in³ = 16.0 in³, or about 262 mL. The CEC count is 172.2 mL because bare bonds and clamps take no space while marrettes do. Don't carry a US box fill result over to a Canadian job, or the other way round. The NEC box fill calculator handles US work.

Maximum conductors by box volume

Box volume divided by the Table 22 space, rounded down, for conductors of one size with nothing else in the box. The two device box volumes are the nominal values used in the RBQ interpretation. The others are common marked volumes, not code values. Take off two conductors for each flush device, one for each pair of marrettes and one for each stud or hickey.

Box14 AWG12 AWG10 AWG8 AWG6 AWG
3 × 2 × 2-1/2 in device box (204 mL)87542
3 × 2 × 3 in device box (245 mL)98653
Marked 300 mL1210864
Marked 350 mL1412974
Marked 400 mL16131085
Marked 500 mL201713116

CEC vs NEC box fill at a glance

ItemCEC Rule 12-3034NEC 314.16
14 AWG allowance24.6 mL2.00 in³ (32.8 mL)
Bare grounds / bondsNot counted1 allowance for all
Wire connectors1 per pairNot counted
Internal cable clampsNot counted1 allowance
Device on a strap2 conductors2 allowances
Deep device32 cm³ per cm of depth if over 2.54 cmNo depth rule; 2 allowances per gang if wider than a 2 in device box
Loops 300 mm or longerNo separate rule2 allowances

Tips from the field

What this calculator does not cover

It does not reproduce the Table 23 conductor counts, which you can use instead for listed box sizes when all conductors are the same size. It does not size pull boxes or junction boxes for 4 AWG and larger conductors, and it uses the largest conductor in the box for every deduction, which can overstate the space needed by a little. Check provincial amendments, such as Quebec's Chapter V, and your inspector's requirements.

Frequently asked questions

How do you calculate box fill in Canada?

Under CEC Rule 12-3034, add the Table 22 space for every insulated conductor that enters or leaves the box (24.6 mL for 14 AWG, 28.7 mL for 12 AWG, 36.9 mL for 10 AWG), then add one conductor of the largest size for each fixture stud or hickey and for every pair of wire connectors, and two conductors for each flush device on a single strap. Compare the total with the volume of the box plus any marked ring or raised cover.

Do bare ground wires count in box fill in Canada?

No. Rule 12-3034 counts insulated conductors only, so the bare bonding conductor in NMD90 cable takes no space allowance. This is one of the main differences from NEC 314.16, which counts all equipment grounding conductors as one allowance.

Do marrettes count in box fill?

Yes. Rule 12-3034(2)(b) deducts one insulated conductor for every pair of conductor connectors with insulating caps, sized by the largest conductor under them. One connector counts as nothing, two or three count as one conductor, four or five as two.

How many 14 AWG wires can go in a 3 × 2 × 2-1/2 device box?

Eight. The box has 204 mL of usable space (the nominal volume used in the RBQ interpretation of Rule 12-3034) and each 14 AWG conductor needs 24.6 mL, so 8 × 24.6 = 196.8 mL fits. A switch takes two of those and a pair of marrettes takes one, which leaves room for five insulated conductors.

How do deep devices such as smart switches and GFCIs affect box fill?

If a device measures more than 2.54 cm from its mounting strap to its back, Rule 12-3034(3) reduces the usable space by 32 cm³ for each centimetre of its depth. A 3.7 cm smart switch takes 118.4 mL, compared with 49.2 mL for an ordinary flush switch on 14 AWG. The RBQ applies this volume instead of the two-conductor deduction.

Do cable clamps count in box fill under the CEC?

No. Rule 12-3034(5) says the usable space disregards space occupied by locknuts, bushings, box connectors and clamps. The NEC instead adds one allowance for internal cable clamps.

Can I add an extension ring or raised cover to get more space?

Yes, if it is marked with its volume. Rule 12-3034(6) adds the marked volume of ganged sections, plaster rings, extension rings and raised covers to the box.

Related calculators, charts and guides