Watts to Amps Calculator

Convert power to current for DC, single-phase and three-phase circuits at any voltage, including 120, 208, 240, 277, 347, 480 and 600 V. You also get the 125% continuous-load current used to size the breaker and wire.

—

Watts to amps formulas

Current equals power divided by voltage. For AC loads, divide by the power factor (PF) too, because a load with PF below 1 draws more current than its watts alone suggest:

DC: A = W ÷ V
AC single phase: A = W ÷ (V × PF)
AC three phase: A = W ÷ (√3 × VL-L × PF) ≈ W ÷ (1.732 × V × PF)

For three phase, the answer is the current in each line, and V is the line-to-line voltage (208, 480 or 600 V). For a 240 V single-phase appliance such as a dryer or water heater, divide by 240, not 120. Each hot leg carries the full current.

Worked examples

1. A 1500 W space heater at 120 V

A = 1500 ÷ 120 = 12.5 A

A heater runs for hours, so treat it as a continuous load. On a 15 A breaker, the continuous limit is 80%, or 12 A, so a 1500 W heater exceeds it; a dedicated 20 A circuit (16 A continuous) has room for it. That is also why a heater on a shared 15 A circuit trips the breaker.

2. A 4500 W water heater at 240 V

A = 4500 ÷ 240 = 18.75 A

NEC 422.13 treats a storage water heater of 120 gallons or less as a continuous load, so the branch circuit must be rated at least 125% of 18.75 A, which is 23.4 A. The next standard breaker is 25 A, and 30 A with 10 AWG copper is also a common choice. Check the run length with the voltage drop calculator.

3. A 10 kW three-phase heater at 208 V

A = 10,000 ÷ (1.732 × 208) = 27.8 A per line

The same heater at 480 V draws 10,000 ÷ (1.732 × 480) = 12.0 A, and at 600 V it draws 9.6 A. Higher voltage means less current and smaller wire for the same power.

4. A 300 W load on a 12 V DC system

A = 300 ÷ 12 = 25 A

Low-voltage DC needs a lot of current for modest power. Voltage drop on long 12 V runs is often the deciding factor, not ampacity.

5. A 2000 W motor load with PF 0.85

A = 2000 ÷ (240 × 0.85) = 9.8 A

At unity power factor the answer would be 8.33 A. Ignoring PF understates the current by about 18% here.

Watts to amps chart (PF = 1)

Single-phase columns use W ÷ V. Three-phase columns use W ÷ (1.732 × V).

Watts12 V DC120 V240 V277 V347 V208 V 3φ480 V 3φ600 V 3φ
100 W8.33 A0.83 A0.42 A0.36 A0.29 A0.28 A0.12 A0.10 A
500 W41.7 A4.17 A2.08 A1.81 A1.44 A1.39 A0.60 A0.48 A
1,000 W83.3 A8.33 A4.17 A3.61 A2.88 A2.78 A1.20 A0.96 A
1,200 W100.0 A10.0 A5.00 A4.33 A3.46 A3.33 A1.44 A1.15 A
1,500 W125.0 A12.5 A6.25 A5.42 A4.32 A4.16 A1.80 A1.44 A
1,800 W150.0 A15.0 A7.50 A6.50 A5.19 A5.00 A2.17 A1.73 A
2,000 W166.7 A16.7 A8.33 A7.22 A5.76 A5.55 A2.41 A1.92 A
2,400 W200.0 A20.0 A10.0 A8.66 A6.92 A6.66 A2.89 A2.31 A
3,000 W250.0 A25.0 A12.5 A10.8 A8.65 A8.33 A3.61 A2.89 A
3,600 W300.0 A30.0 A15.0 A13.0 A10.4 A9.99 A4.33 A3.46 A
4,000 W333.3 A33.3 A16.7 A14.4 A11.5 A11.1 A4.81 A3.85 A
4,500 W375.0 A37.5 A18.8 A16.2 A13.0 A12.5 A5.41 A4.33 A
5,000 W416.7 A41.7 A20.8 A18.1 A14.4 A13.9 A6.01 A4.81 A
7,200 W600.0 A60.0 A30.0 A26.0 A20.7 A20.0 A8.66 A6.93 A
9,600 W800.0 A80.0 A40.0 A34.7 A27.7 A26.6 A11.5 A9.24 A
10,000 W833.3 A83.3 A41.7 A36.1 A28.8 A27.8 A12.0 A9.62 A

277 V and 480 V are common for lighting and motors in US commercial buildings. 347 V and 600 V are the Canadian equivalents.

Circuit capacity in watts

Going the other way is just as useful: how much can a circuit carry? Multiply the breaker rating by the voltage, then take 80% for continuous loads.

BreakerVoltsMaximum wattsContinuous (80%)
15 A120 V1,800 W1,440 W
20 A120 V2,400 W1,920 W
15 A240 V3,600 W2,880 W
20 A240 V4,800 W3,840 W
30 A240 V7,200 W5,760 W
40 A240 V9,600 W7,680 W
50 A240 V12,000 W9,600 W

The continuous-load rule in the US and Canada

The two codes say the same thing from opposite directions. In the US, NEC 210.19(A) and 210.20(A) require the conductor and breaker to be rated at least 125% of a continuous load, meaning one that runs for three hours or more. In Canada, CEC Rule 8-104 limits a continuous load to 80% of the rating of a standard breaker, or 100% for an assembly marked for continuous operation at 100%. Since 1 ÷ 1.25 = 0.8, both rules land on the same breaker for the same load.

After you have the current, pick the conductor with the wire size calculator (NEC) or the wire size calculator for Canada (CEC), and check the run with the CEC voltage drop calculator if you work in Canada.

Watts, VA and amps

Nameplates on motors, transformers, UPS units and LED drivers often list VA or kVA instead of watts. For VA, skip the power factor: A = VA ÷ V, or VA ÷ (1.732 × V) for three phase. Use the kVA calculator for transformer full-load current, and the amps to watts calculator to convert back.

Common mistakes

Frequently asked questions

How do I convert watts to amps?

Divide watts by volts. DC: A = W ÷ V. Single-phase AC: A = W ÷ (V × PF). Three-phase AC: A = W ÷ (√3 × V × PF), using the line-to-line voltage. For heaters and other resistive loads, PF = 1.

How many amps is 1500 watts?

1500 W ÷ 120 V = 12.5 A. At 240 V the same 1500 W is 6.25 A. A 1500 W plug-in heater on a 15 A, 120 V circuit already uses 12.5 A, which is more than the 12 A that 80% of a 15 A breaker allows for a continuous load.

How many amps is 1000 watts?

1000 ÷ 120 = 8.33 A at 120 V, and 1000 ÷ 240 = 4.17 A at 240 V.

How many watts can a 15 A or 20 A circuit carry?

At 120 V, a 15 A circuit is 1800 W and a 20 A circuit is 2400 W. For loads that run three hours or more, both the NEC (210.19 and 210.20, the 125% rule) and the CEC (Rule 8-104, the 80% rule for standard breakers) bring that down to 1440 W and 1920 W.

Is the answer different in Canada?

The math is identical. Homes in both countries are supplied at 120/240 V. In commercial buildings you will more often see 120/208 V and 347/600 V in Canada, and 120/208 V and 277/480 V in the US. The table below covers all of these.

Why does my motor draw more amps than the formula says?

Motor nameplates rate output power at the shaft, not input power. Input current includes losses and power factor, so a 746 W (1 hp) motor draws more than 746 ÷ V amps. For motor circuits, the NEC (430.6) and CEC both size conductors from the full-load current tables, not from a watts conversion.