What Size Wire for 100 Amps?

3 AWG copper or 1 AWG aluminum for a 100 A circuit or feeder (NEC Table 310.16, 75 °C column). Below: the 60 °C and dwelling service answers, how far each size can run at 120/240 V and three phase, the ground and conduit size, and the rules that change the answer.

Quick answer: wire size for a 100 amp breaker

Minimum conductor for 100 A with not more than three current-carrying conductors at 30 °C (86 °F) ambient.

Wire and terminal ratingMinimum sizeTable ampacity
Copper, 60 °C column (NM cable, unmarked terminals)1 AWG110 A
Copper, 75 °C column (THHN/THWN-2, 75 °C terminals)3 AWG100 A
Aluminum, 60 °C column1/0 AWG100 A
Aluminum, 75 °C column (XHHW-2, SER, 75 °C terminals)1 AWG100 A

Most 100 A breakers and panelboards are marked 60/75 °C, so the 75 °C column applies when the wire is also rated 75 °C or higher (NEC 110.14(C)(1)(a) lets circuits of 100 A or less use 75 °C ampacity only when the equipment is listed and marked for it). NM cable is held to the 60 °C column by NEC 334.80. The 90 °C column (115 A for 3 AWG copper) is only a starting point for derating and cannot be used at the terminals.

100 amp service vs 100 amp subpanel

InstallationCopperAluminumRule
Dwelling service or main feeder, 120/240 V, carrying the whole house load4 AWG2 AWGNEC 310.12: 83% of 100 A = 83 A
Subpanel feeder, detached garage, shop or any non-dwelling service3 AWG1 AWGTable 310.16, 75 °C, full 100 A
NM or SE cable held to 60 °C1 AWG1/0 AWGTable 310.16, 60 °C

The 83% rule is the most common source of confusion. It only applies to a single-phase dwelling service or the feeder that carries the entire dwelling load, so a 100 A subpanel fed from a 200 A main panel needs the full-size 3 AWG copper or 1 AWG aluminum. A feeder to a subpanel also needs four wires (two hots, an insulated neutral and an equipment ground), because NEC 250.24(A)(5) and 250.142(B) keep the neutral and ground separate after the service disconnect.

Wire size for 100 amps by distance (240 V)

Smallest size that keeps a 120/240 V single-phase run at or under a 3% voltage drop. The 80 A columns are for a continuous or typical load on a 100 A breaker. Ampacity still sets the floor, so the table never goes below 3 AWG copper or 1 AWG aluminum.

One-way run length. 3% drop at 240 V, NEC Chapter 9 Table 8 resistance at 75 °C.
RunCu, 100 ACu, 80 AAl, 100 AAl, 80 A
50 ft3 AWG3 AWG1 AWG1 AWG
75 ft3 AWG3 AWG1 AWG1 AWG
100 ft3 AWG3 AWG1 AWG1 AWG
125 ft3 AWG3 AWG1 AWG1 AWG
150 ft2 AWG3 AWG1/0 AWG1 AWG
200 ft1 AWG2 AWG2/0 AWG1/0 AWG
250 ft1/0 AWG1 AWG3/0 AWG2/0 AWG
300 ft2/0 AWG1/0 AWG4/0 AWG3/0 AWG

Example: a 100 A subpanel in a detached shop 250 ft from the house, with an expected load of 80 A at 240 V. 3 AWG copper only reaches 183 ft at 80 A and 2 AWG reaches 231 ft, so the run needs 1 AWG copper, which reaches 292 ft. In aluminum, 1/0 reaches 223 ft and 2/0 reaches 283 ft, so 2/0 aluminum. Because the hots were upsized, the 8 AWG copper ground must be upsized in proportion (see ground).

Maximum length at 100 amps by wire size

The longest one-way run, in feet, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are DC resistance figures; for large conductors in steel conduit at a low power factor, reactance adds a little more drop.

Copper

Size240 V, 3%240 V at 80 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
3 AWG146183244147339
2 AWG185231309185428
1 AWG233292389233539
1/0 AWG295368491295681
2/0 AWG372465620372859
3/0 AWG4695877834701085
4/0 AWG5927409865921367
250 kcmil69987311656991614

Aluminum

Size240 V, 3%240 V at 80 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
1 AWG142177237142328
1/0 AWG179223298179413
2/0 AWG226283377226522
3/0 AWG285357476285659
4/0 AWG359449600360831
250 kcmil425531708425981
300 kcmil5096368485091175
350 kcmil5957439915951374

NEC 215.2(A)(1) Informational Note 2 recommends 3% on a feeder and 5% total to the farthest outlet. A 3% drop at 240 V is 7.2 V. Use the voltage drop calculator for your exact load, or the three-phase voltage drop calculator for 208 to 600 V.

Ground wire for 100 amps

Conduit size for 100 amp wire

Smallest conduit at 40% fill (NEC Chapter 9 Table 1) using THHN/THWN-2 areas from Chapter 9 Table 5. "Three wires" is two hots and a neutral; "four wires" adds a second neutral or a third phase.

RunConductorsArea, in²EMTPVC 40EMT, 4 wires
Feeder, copper 75 °C3 × 3 AWG + 8 AWG0.329111-1/4
Feeder, aluminum 75 °C3 × 1 AWG + 6 AWG0.5191-1/41-1/41-1/2
Dwelling service (310.12), copper3 × 4 AWG + 8 AWG0.284111-1/4
Dwelling service (310.12), aluminum3 × 2 AWG + 6 AWG0.3981-1/41-1/41-1/4
Upsized for distance (250 ft example), copper3 × 1 AWG + 4 AWG0.5511-1/41-1/41-1/2

XHHW-2 aluminum has slightly different areas than THHN, so check the conduit fill calculator for your insulation. Many electricians go one trade size up for an easier pull on long runs.

How much load can a 100 amp circuit carry?

SystemAt 100 AContinuous (80 A)
120 V single phase12.0 kW9.6 kW
240 V single phase24.0 kW19.2 kW
208 V three phase36.0 kW28.8 kW
480 V three phase83.1 kW66.5 kW
600 V three phase103.9 kW83.1 kW

Loads that run three hours or more must be sized at 125% under NEC 210.19(A) and 215.2(A)(1), which limits a 100 A breaker to 80 A of continuous load. The 240 V figures assume a balanced load and unity power factor. The amps to watts calculator handles power factor.

When more than three wires share a conduit

With four to six current-carrying conductors in one raceway, NEC 310.15(C)(1) cuts ampacity to 80%. Starting from the 90 °C column, 3 AWG copper drops to 92 A and 2 AWG copper to 104 A, so a 100 A circuit in a shared conduit needs 2 AWG copper. Hot attics and rooftops add an ambient correction too; see wire derating.

In Canada

CEC Table 2 (copper) and Table 4 (aluminum) give the same ampacities for these sizes, so 3 AWG copper or 1 AWG aluminum carries 100 A at 75 °C. Canada does not use the NEC 310.12 83% rule; single-dwelling service conductors have their own minimum sizes in CEC Table 39, so check the CEC before sizing a Canadian service. Rule 8-102 makes the 3% and 5% voltage drop limits mandatory. Use the Canadian wire size calculator for distances in metres.

This page is a quick reference. Confirm against the code edition your jurisdiction has adopted, the equipment markings and your inspector.

Frequently asked questions

What size wire for 100 amps?

3 AWG copper or 1 AWG aluminum, using the 75 °C column of NEC Table 310.16 (both are rated 100 A). If the terminals or the cable are limited to 60 °C, such as NM cable, you need 1 AWG copper (110 A) or 1/0 aluminum (100 A).

What size wire for a 100 amp subpanel?

A subpanel feeder is not covered by the 310.12 83% rule, so size for the full 100 A: 3 AWG copper THHN or 1 AWG aluminum with 75 °C terminals at both ends, four wires (two hots, a neutral and a separate ground) plus an 8 AWG copper or 6 AWG aluminum equipment ground. On runs longer than about 100 ft, check voltage drop with the tables on this page.

What size wire for 100 amp service?

For a 120/240 V dwelling service that carries the whole house load, NEC 310.12 lets the conductors be rated at 83% of the service, so 4 AWG copper or 2 AWG aluminum is enough. For any other service or feeder, use the 75 °C column: 3 AWG copper or 1 AWG aluminum.

Can I use 2 AWG aluminum for a 100 amp subpanel?

No. 2 AWG aluminum is rated 90 A at 75 °C, and because 90 A is itself a standard breaker size, the NEC 240.4(B) next-size-up rule does not let it go on a 100 A breaker. 2 AWG aluminum is used for a 100 A dwelling service under 310.12, which does not apply to a subpanel. Use 1 AWG aluminum.

How far can you run 3 AWG copper at 100 amps?

About 146 ft one way at 240 V with a full 100 A load before the drop passes 3%, or 183 ft at an 80 A load. At a 5% total limit the full-load figure is 244 ft. These use the 75 °C resistance in NEC Chapter 9 Table 8 (0.245 ohms per 1000 ft).

What size ground wire for a 100 amp subpanel?

8 AWG copper or 6 AWG aluminum, from NEC Table 250.122 for a 100 A overcurrent device. If you upsize the hot conductors for voltage drop, 250.122(B) requires the ground to be upsized by the same proportion of circular mil area.

What size conduit for 100 amp wire?

Three 3 AWG copper THHN (two hots and a neutral) and an 8 AWG copper ground fit in 1 inch EMT or PVC Schedule 40 at 40% fill. Four 3 AWG conductors plus the ground need 1-1/4 inch EMT. Three 1 AWG aluminum and a 6 AWG aluminum ground need 1-1/4 inch. The conduit table on this page shows the area math.

Related calculators, charts and guides