What Size Wire for 200 Amps?

3/0 copper or 250 kcmil aluminum for a 200 A feeder (NEC Table 310.16, 75 °C column), or 2/0 copper or 4/0 aluminum for a 120/240 V dwelling service under NEC 310.12. Below: wire size by distance to 500 ft, maximum run lengths at 240 V and three phase, the ground, the conduit and the load a 200 A circuit carries.

Quick answer: wire size for a 200 amp breaker

Minimum conductor for 200 A with not more than three current-carrying conductors at 30 °C (86 °F) ambient.

Wire and terminal ratingMinimum sizeTable ampacity
Copper, 75 °C column (THHN/THWN-2, 75 °C terminals)3/0 AWG200 A
Aluminum, 75 °C column (XHHW-2, SER, 75 °C terminals)250 kcmil205 A
Copper, 60 °C column (equipment marked 60 °C only)250 kcmil215 A
Aluminum, 60 °C column (equipment marked 60 °C only)350 kcmil210 A

For circuits over 100 A, NEC 110.14(C)(1)(b) lets you use the 75 °C column unless the equipment is marked otherwise, so the 75 °C answer is the normal one. The 90 °C column (225 A for 3/0 copper, 230 A for 250 kcmil aluminum) is a starting point for derating only and cannot be used at the terminals.

200 amp service vs 200 amp subpanel

InstallationCopperAluminumRule
Dwelling service or main feeder, 120/240 V, carrying the whole house load2/0 AWG4/0 AWGNEC 310.12: 83% of 200 A = 166 A
Subpanel feeder, detached garage or shop, commercial or three-phase service3/0 AWG250 kcmilTable 310.16, 75 °C, full 200 A
Four to six current-carrying conductors in one raceway4/0 AWG300 kcmil310.15(C)(1) 80% from 90 °C: 208 A and 208 A

The 83% rule only applies to a single-phase dwelling service, or the feeder that carries the entire dwelling load. A 200 A subpanel fed from a 400 A service (for example, one side of a 320/400 A meter base), a shop panel, or any three-phase service needs the full 3/0 copper or 250 kcmil aluminum. A feeder to a subpanel also needs four wires, because NEC 250.24(A)(5) and 250.142(B) keep the neutral and ground separate after the service disconnect.

Wire size for 200 amps by distance (240 V)

Smallest size that keeps a 120/240 V single-phase run at or under a 3% voltage drop. The 160 A columns are the continuous-load limit of a 200 A breaker and a realistic design load for many subpanels. Ampacity sets the floor, so the table never goes below 3/0 copper or 250 kcmil aluminum.

One-way run length. 3% drop at 240 V, NEC Chapter 9 Table 8 resistance at 75 °C.
RunCu, 200 ACu, 160 AAl, 200 AAl, 160 A
50 ft3/0 AWG3/0 AWG250 kcmil250 kcmil
100 ft3/0 AWG3/0 AWG250 kcmil250 kcmil
150 ft3/0 AWG3/0 AWG250 kcmil250 kcmil
200 ft3/0 AWG3/0 AWG250 kcmil250 kcmil
250 ft4/0 AWG3/0 AWG300 kcmil250 kcmil
300 ft250 kcmil4/0 AWG400 kcmil300 kcmil
400 ft300 kcmil250 kcmil500 kcmil400 kcmil
500 ft400 kcmil300 kcmil600 kcmil500 kcmil

Example: a 200 A subpanel in an outbuilding 300 ft from the service, with an expected load of 160 A at 240 V. 3/0 copper reaches only 293 ft at 160 A, so the run needs 4/0 AWG copper, which reaches 370 ft. In aluminum, 250 kcmil reaches 265 ft, so the answer is 300 kcmil aluminum (318 ft). Because the hots were upsized, the ground grows too (see ground).

Maximum length at 200 amps by wire size

The longest one-way run, in feet, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are DC resistance figures; for large conductors in steel conduit at a low power factor, reactance adds a little more drop.

Copper

Size240 V, 3%240 V at 160 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
3/0 AWG234293391235542
4/0 AWG296370493296683
250 kcmil349436582349807
300 kcmil419524699419968
350 kcmil4906138174901132
400 kcmil5607009345611294
500 kcmil69787211626981611
600 kcmil841105114018411942

Aluminum

Size240 V, 3%240 V at 160 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
4/0 AWG *179224300180415
250 kcmil212265354212490
300 kcmil254318424254587
350 kcmil297371495297687
400 kcmil340425567340785
500 kcmil424530707424980
600 kcmil5096378495101177

* 4/0 aluminum is 180 A at 75 °C. It is shown for 120/240 V dwelling services under 310.12; it is not a full 200 A feeder conductor. NEC 215.2(A)(1) Informational Note 2 recommends 3% on a feeder and 5% total to the farthest outlet. A 3% drop is 7.2 V at 240 V, 6.24 V at 208 V and 14.4 V at 480 V. Use the voltage drop calculator for your exact load, or the three-phase voltage drop calculator for 208 to 600 V.

Ground wire for 200 amps

Conduit size for 200 amp wire

Smallest conduit at 40% fill (NEC Chapter 9 Table 1) using THHN/THWN-2 areas from Chapter 9 Table 5. "Three wires" is two hots and a neutral; "four wires" adds a third phase or a second neutral. Service rows include a ground-size wire for comparison.

RunConductorsArea, in²EMTPVC 40EMT, 4 wires
Feeder, copper 75 °C3 × 3/0 AWG + 6 AWG0.854222
Feeder, aluminum 75 °C3 × 250 kcmil + 4 AWG1.273222-1/2
Dwelling service (310.12), copper3 × 2/0 AWG + 6 AWG0.7181-1/21-1/22
Dwelling service (310.12), aluminum3 × 4/0 AWG + 4 AWG1.053222-1/2
Upsized for distance (300 ft example), copper3 × 4/0 AWG + 4 AWG1.053222-1/2

XHHW-2 aluminum has slightly different areas than THHN, so check the conduit fill calculator for your insulation. Long or bendy runs pull easier one trade size up.

How much load can a 200 amp circuit carry?

SystemAt 200 AContinuous (160 A)
120/240 V single phase (240 V load)48.0 kW38.4 kW
208 V three phase72.1 kW57.6 kW
240 V three phase83.1 kW66.5 kW
480 V three phase166.3 kW133.0 kW
600 V three phase207.8 kW166.3 kW

Loads that run three hours or more must be sized at 125% under NEC 210.19(A) and 215.2(A)(1), which limits a 200 A breaker to 160 A of continuous load. Figures assume a balanced load and unity power factor. The amps to watts calculator handles power factor, and the kVA calculator covers transformers and services.

When more than three wires share a conduit

With four to six current-carrying conductors in one raceway, NEC 310.15(C)(1) cuts ampacity to 80%. Starting from the 90 °C column, 3/0 copper drops to 180 A and 4/0 copper to 208 A, so a 200 A circuit in a shared conduit needs 4/0 copper. In aluminum, 250 kcmil drops to 184 A and 300 kcmil to 208 A. Hot rooftops add an ambient correction too; see wire derating.

In Canada

CEC Table 2 (copper) and Table 4 (aluminum) give the same 75 °C ampacities for these sizes, so 3/0 copper (200 A) or 250 kcmil aluminum (205 A) carries 200 A. Canada does not use the NEC 310.12 83% rule; single-dwelling service conductors have their own minimum sizes in CEC Table 39, so check the CEC before sizing a Canadian service. Rule 8-102 makes the 3% and 5% voltage drop limits mandatory, and the Canadian voltage drop tables give 200 A feeder lengths in metres. Use the Canadian wire size calculator for your run.

For smaller feeders, see wire size for 100 amps.

This page is a quick reference. Confirm against the code edition your jurisdiction has adopted, the equipment markings and your inspector.

Frequently asked questions

What size wire for 200 amps?

3/0 AWG copper (200 A) or 250 kcmil aluminum (205 A), from the 75 °C column of NEC Table 310.16. For a 120/240 V dwelling service that carries the whole house load, NEC 310.12 allows 2/0 copper or 4/0 aluminum instead.

What size wire for a 200 amp service?

For a single-phase 120/240 V dwelling service, NEC 310.12 lets the service conductors be sized at 83% of the rating, 166 A, so 2/0 copper (175 A) or 4/0 aluminum (180 A) is enough. For a commercial or three-phase service, use the full 200 A: 3/0 copper or 250 kcmil aluminum.

What size wire for a 200 amp subpanel?

A subpanel feeder does not qualify for the 310.12 83% rule unless it carries the entire dwelling load, so size it for 200 A: 3/0 copper or 250 kcmil aluminum at 75 °C, with two hots, an insulated neutral and a separate equipment ground of 6 AWG copper or 4 AWG aluminum (NEC Table 250.122). On runs over about 200 ft, check voltage drop with the tables on this page.

Can I use 4/0 aluminum for 200 amps?

Yes for a 120/240 V dwelling service or main feeder carrying the whole house load, under NEC 310.12. For other feeders, 4/0 aluminum is 180 A at 75 °C. NEC 240.4(B) lets a conductor whose ampacity is not a standard breaker rating be protected by the next higher standard size (200 A) on circuits up to 800 A, but the feeder still has to carry its calculated load under 215.2, so the load must be 180 A or less. 250 kcmil aluminum meets 200 A outright.

How far can you run 3/0 copper at 200 amps?

About 234 ft one way at 240 V with a full 200 A load before the drop passes 3%, or 293 ft at a 160 A load. At a 5% total limit the full-load figure is 391 ft. These use the 75 °C resistance in NEC Chapter 9 Table 8 (0.0766 ohms per 1000 ft).

What size ground wire for 200 amp service?

The grounding electrode conductor for 2/0 or 3/0 copper (or 4/0 or 250 kcmil aluminum) service conductors is 4 AWG copper or 2 AWG aluminum, from NEC Table 250.66. The conductor to a ground rod never has to be larger than 6 AWG copper (250.66(A)). The equipment grounding conductor for a 200 A feeder is 6 AWG copper or 4 AWG aluminum (Table 250.122).

What size conduit for 200 amp wire?

Three 3/0 copper THHN and a 6 AWG copper ground fit in 2 inch EMT or PVC Schedule 40 at 40% fill. Three 250 kcmil aluminum and a 4 AWG ground also need 2 inch. The conduit table on this page shows the area math for service, feeder and upsized runs.

What size wire for 200 amps 300 feet away?

For a 160 A load at 240 V and a 3% drop, 4/0 AWG copper or 300 kcmil aluminum. At a full 200 A, 250 kcmil copper or 400 kcmil aluminum. Upsizing the hots also upsizes the equipment ground under 250.122(B).