Quick answer: wire size for a 100 A breaker in Canada
Minimum conductor for 100 A, not more than three conductors in a raceway or cable, 30 °C ambient.
| Conductor and termination rating | Minimum size | Ampacity |
|---|---|---|
| Copper, 75 °C (T90, TECK90 or RW90 on 75 °C terminals) | 3 AWG | 100 A (Table 2) |
| Copper, 60 °C (unmarked equipment rated 100 A or less) | 1 AWG | 110 A (Table 2) |
| Aluminum, 75 °C (ACWU90, RW90 on 75 °C terminals) | 1 AWG | 100 A (Table 4) |
Rule 4-006 sets which column you can use. Where equipment is marked with a termination temperature, use that column. Where it is not marked, equipment rated 100 A or less (or marked for 1 AWG and smaller conductors) is treated as 60 °C, and equipment rated more than 100 A as 75 °C. Most Canadian breakers and panelboards are marked 75 °C, so a 90 °C conductor is still sized from the 75 °C column, at least for the first 1.2 m from the termination. The 90 °C value (115 A for 3 AWG copper) matters only as a starting point for correction factors. See the CEC Table 2 chart for Table 5A (hot locations) and Table 5C (more than three conductors).
100 amp service in a house
| Installation | Copper | Aluminum | Rule |
|---|---|---|---|
| Single-dwelling service, 120/240 V | 3 AWG | 1 AWG | Tables 2 and 4, 75 °C; no 83% reduction |
| Feeder to a subpanel, garage or shop | 3 AWG | 1 AWG | Tables 2 and 4, 75 °C |
| Equipment limited to 60 °C | 1 AWG | see Table 4 | Table 2, 60 °C |
Rule 8-200 sets the minimum ampacity of a single dwelling's service or feeder conductors as the larger of a calculated load (5,000 W for the first 90 m² of living area, 1,000 W for each extra 90 m², plus heating, air conditioning, range, EV charging and other loads at their demand factors) or a floor: 100 A if the floor area, excluding the basement, is 80 m² or more, and 60 A if it is less. So most Canadian houses need at least a 100 A service, and many with electric heat, EV charging or a heat pump calculate higher. The 200 amp guide covers the next step up.
Wire size for 100 amps by distance (metres, 240 V)
Smallest size that keeps a 120/240 V single-phase run at or under the Rule 8-102 3% limit. The 80 A columns use the Rule 8-102 default for an unknown load (80% of a 100 A breaker); the 100 A columns are for a known full load. Ampacity sets the floor, so the table never goes below 3 AWG copper or 1 AWG aluminum.
| Run | Cu, 80 A | Cu, 100 A | Al, 80 A | Al, 100 A |
|---|---|---|---|---|
| 15 m | 3 AWG | 3 AWG | 1 AWG | 1 AWG |
| 20 m | 3 AWG | 3 AWG | 1 AWG | 1 AWG |
| 30 m | 3 AWG | 3 AWG | 1 AWG | 1 AWG |
| 40 m | 3 AWG | 3 AWG | 1 AWG | 1 AWG |
| 50 m | 3 AWG | 2 AWG | 1 AWG | 1/0 AWG |
| 60 m | 2 AWG | 1 AWG | 1/0 AWG | 2/0 AWG |
| 75 m | 1 AWG | 1/0 AWG | 2/0 AWG | 3/0 AWG |
| 90 m | 1/0 AWG | 2/0 AWG | 3/0 AWG | 4/0 AWG |
Example: a 100 A subpanel in a detached garage 45 m from the house, load not yet known. Rule 8-102 says to use 80 A. 3 AWG copper reaches 55 m at 80 A, so it works. At 75 m, 3 AWG (55 m) and 2 AWG (70 m) both fall short and 1 AWG copper (89 m) is needed. Remember the 5% total limit includes the service conductors and the branch circuits after the subpanel.
Maximum length at 100 amps by wire size
The longest one-way run, in metres, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are resistance-only figures; large conductors in steel raceway at a low power factor see a little more drop from reactance.
Copper
| Size | 240 V, 80 A, 3% | 240 V, 100 A, 3% | 240 V, 80 A, 5% | 208 V 3-ph, 80 A, 3% | 600 V 3-ph, 80 A, 3% |
|---|---|---|---|---|---|
| 3 AWG | 55 | 44 | 93 | 56 | 161 |
| 2 AWG | 70 | 56 | 117 | 70 | 204 |
| 1 AWG | 89 | 71 | 148 | 89 | 257 |
| 1/0 AWG | 112 | 89 | 187 | 112 | 324 |
| 2/0 AWG | 141 | 113 | 236 | 141 | 409 |
| 3/0 AWG | 179 | 143 | 298 | 179 | 516 |
| 4/0 AWG | 225 | 180 | 375 | 225 | 651 |
| 250 kcmil | 266 | 213 | 443 | 266 | 768 |
Aluminum
| Size | 240 V, 80 A, 3% | 240 V, 100 A, 3% | 240 V, 80 A, 5% | 208 V 3-ph, 80 A, 3% | 600 V 3-ph, 80 A, 3% |
|---|---|---|---|---|---|
| 1 AWG | 54 | 43 | 90 | 54 | 156 |
| 1/0 AWG | 68 | 54 | 113 | 68 | 196 |
| 2/0 AWG | 86 | 69 | 143 | 86 | 249 |
| 3/0 AWG | 108 | 87 | 181 | 108 | 314 |
| 4/0 AWG | 137 | 109 | 228 | 137 | 395 |
| 250 kcmil | 161 | 129 | 269 | 162 | 467 |
| 300 kcmil | 194 | 155 | 323 | 194 | 560 |
| 350 kcmil | 226 | 181 | 377 | 226 | 654 |
The 5% column is the whole budget from the supply side of the service to the farthest point of use, so in practice a feeder rarely gets all of it. For your exact load and length, use the Canadian voltage drop calculator or the Canadian wire size calculator, which checks ampacity and Rule 8-102 together.
Bonding and grounding conductors for 100 amps
- Bonding conductor (Table 16, Rule 10-616): 8 AWG copper or 6 AWG aluminum for an overcurrent device up to 100 A.
- Upsized for voltage drop: when the circuit conductors are increased to compensate for voltage drop, size the bonding conductor from the ampacity of the largest ungrounded conductor instead. The table below shows what that means for common upsizes.
- Service bonding: at service equipment, Table 16 is entered with the ampacity of the largest ungrounded conductor. For 3 AWG copper (100 A), that is 8 AWG copper.
- Grounding conductor to the electrode (Rule 10-114): not smaller than 6 AWG copper or 4 AWG aluminum, and that size covers every common service size.
| Copper circuit conductor | Table 2 ampacity, 75 °C | Copper bonding conductor (Table 16) |
|---|---|---|
| 3 AWG | 100 A | 8 AWG |
| 2 AWG | 115 A | 6 AWG |
| 1 AWG | 130 A | 6 AWG |
| 1/0 AWG | 150 A | 6 AWG |
| 2/0 AWG | 175 A | 6 AWG |
How much load can a 100 amp circuit carry?
| System | At 100 A | At 80 A |
|---|---|---|
| 120 V single phase | 12.0 kW | 9.6 kW |
| 240 V single phase (120/240 V) | 24.0 kW | 19.2 kW |
| 208 V three phase (120/208 V) | 36.0 kW | 28.8 kW |
| 600 V three phase (347/600 V) | 103.9 kW | 83.1 kW |
The figures assume a balanced load and unity power factor. A 100 A service at 240 V is 24 kW, which is exactly the Rule 8-200 minimum load for a dwelling of 80 m² or more. Continuous loads on breakers not marked for 100% continuous operation are generally limited to 80% of the rating under Rule 8-104. The amps to watts calculator handles power factor.
CEC vs NEC for 100 amps
The raw ampacities in CEC Tables 2 and 4 match NEC Table 310.16 for these sizes, so the basic answer (3 AWG copper, 1 AWG aluminum) is the same in both countries. The differences: Canada has no 83% dwelling service rule, voltage drop is mandatory under Rule 8-102 rather than an informational note, run lengths and the code itself are in metres, bonding conductors come from Table 16 instead of NEC Table 250.122 (same 8 AWG Cu / 6 AWG Al at 100 A), and provinces adopt different editions: CSA C22.1:24 in Alberta and Saskatchewan, the 2024 Ontario Electrical Safety Code in Ontario, the BC Electrical Code 2024 in British Columbia, and CSA C22.1:21 with amendments in Quebec. For the US version of this page, see wire size for 100 amps (NEC).
Sources
- VRI Electrical, Cable Ampacity Tables – CEC / CSA C22.1 (Tables 2 and 4)
- CSA Group, CEC Section 8 excerpt (Rule 8-102)
- Electrical Industry News Week, Guide to the CE Code, Section 8 and Section 4 (Rules 8-200, 4-006)
- City of Fort Saskatchewan, Load calculation form (Rule 8-200 1) b) 100 A / 60 A minimums)
- IAEI Magazine, Application of Rule 4-006
- SparkShift, CEC Rule 10-114 and Table 16 (grounding and bonding sizes, provincial editions)
- Conductor resistance: NEC Chapter 9 Table 8 values at 75 °C, converted to metres