What Size Wire for 100 Amps in Canada? (CEC)

3 AWG copper or 1 AWG aluminum for a 100 A service, feeder or subpanel under the Canadian Electrical Code (Table 2 and Table 4, 75 °C column). Below: the 60 °C answer, the Rule 8-200 service minimum, wire size by distance in metres under Rule 8-102, max run lengths at 120/240, 208 and 600 V, and the Table 16 bonding conductor.

CEC data notice: CEC values were checked against public summaries of CSA C22.1:24, not the code book itself. Conduit and conductor areas use NEC Chapter 9 data, and some aluminum kcmil ampacities are unverified. Confirm against the CEC edition and provincial amendments adopted where you work.

Quick answer: wire size for a 100 A breaker in Canada

Minimum conductor for 100 A, not more than three conductors in a raceway or cable, 30 °C ambient.

Conductor and termination ratingMinimum sizeAmpacity
Copper, 75 °C (T90, TECK90 or RW90 on 75 °C terminals)3 AWG100 A (Table 2)
Copper, 60 °C (unmarked equipment rated 100 A or less)1 AWG110 A (Table 2)
Aluminum, 75 °C (ACWU90, RW90 on 75 °C terminals)1 AWG100 A (Table 4)

Rule 4-006 sets which column you can use. Where equipment is marked with a termination temperature, use that column. Where it is not marked, equipment rated 100 A or less (or marked for 1 AWG and smaller conductors) is treated as 60 °C, and equipment rated more than 100 A as 75 °C. Most Canadian breakers and panelboards are marked 75 °C, so a 90 °C conductor is still sized from the 75 °C column, at least for the first 1.2 m from the termination. The 90 °C value (115 A for 3 AWG copper) matters only as a starting point for correction factors. See the CEC Table 2 chart for Table 5A (hot locations) and Table 5C (more than three conductors).

100 amp service in a house

InstallationCopperAluminumRule
Single-dwelling service, 120/240 V3 AWG1 AWGTables 2 and 4, 75 °C; no 83% reduction
Feeder to a subpanel, garage or shop3 AWG1 AWGTables 2 and 4, 75 °C
Equipment limited to 60 °C1 AWGsee Table 4Table 2, 60 °C

Rule 8-200 sets the minimum ampacity of a single dwelling's service or feeder conductors as the larger of a calculated load (5,000 W for the first 90 m² of living area, 1,000 W for each extra 90 m², plus heating, air conditioning, range, EV charging and other loads at their demand factors) or a floor: 100 A if the floor area, excluding the basement, is 80 m² or more, and 60 A if it is less. So most Canadian houses need at least a 100 A service, and many with electric heat, EV charging or a heat pump calculate higher. The 200 amp guide covers the next step up.

Wire size for 100 amps by distance (metres, 240 V)

Smallest size that keeps a 120/240 V single-phase run at or under the Rule 8-102 3% limit. The 80 A columns use the Rule 8-102 default for an unknown load (80% of a 100 A breaker); the 100 A columns are for a known full load. Ampacity sets the floor, so the table never goes below 3 AWG copper or 1 AWG aluminum.

One-way run length. 3% drop (7.2 V) at 240 V, conductor resistance at 75 °C.
RunCu, 80 ACu, 100 AAl, 80 AAl, 100 A
15 m3 AWG3 AWG1 AWG1 AWG
20 m3 AWG3 AWG1 AWG1 AWG
30 m3 AWG3 AWG1 AWG1 AWG
40 m3 AWG3 AWG1 AWG1 AWG
50 m3 AWG2 AWG1 AWG1/0 AWG
60 m2 AWG1 AWG1/0 AWG2/0 AWG
75 m1 AWG1/0 AWG2/0 AWG3/0 AWG
90 m1/0 AWG2/0 AWG3/0 AWG4/0 AWG

Example: a 100 A subpanel in a detached garage 45 m from the house, load not yet known. Rule 8-102 says to use 80 A. 3 AWG copper reaches 55 m at 80 A, so it works. At 75 m, 3 AWG (55 m) and 2 AWG (70 m) both fall short and 1 AWG copper (89 m) is needed. Remember the 5% total limit includes the service conductors and the branch circuits after the subpanel.

Maximum length at 100 amps by wire size

The longest one-way run, in metres, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are resistance-only figures; large conductors in steel raceway at a low power factor see a little more drop from reactance.

Copper

Size240 V, 80 A, 3%240 V, 100 A, 3%240 V, 80 A, 5%208 V 3-ph, 80 A, 3%600 V 3-ph, 80 A, 3%
3 AWG55449356161
2 AWG705611770204
1 AWG897114889257
1/0 AWG11289187112324
2/0 AWG141113236141409
3/0 AWG179143298179516
4/0 AWG225180375225651
250 kcmil266213443266768

Aluminum

Size240 V, 80 A, 3%240 V, 100 A, 3%240 V, 80 A, 5%208 V 3-ph, 80 A, 3%600 V 3-ph, 80 A, 3%
1 AWG54439054156
1/0 AWG685411368196
2/0 AWG866914386249
3/0 AWG10887181108314
4/0 AWG137109228137395
250 kcmil161129269162467
300 kcmil194155323194560
350 kcmil226181377226654

The 5% column is the whole budget from the supply side of the service to the farthest point of use, so in practice a feeder rarely gets all of it. For your exact load and length, use the Canadian voltage drop calculator or the Canadian wire size calculator, which checks ampacity and Rule 8-102 together.

Bonding and grounding conductors for 100 amps

Copper circuit conductorTable 2 ampacity, 75 °CCopper bonding conductor (Table 16)
3 AWG100 A8 AWG
2 AWG115 A6 AWG
1 AWG130 A6 AWG
1/0 AWG150 A6 AWG
2/0 AWG175 A6 AWG

How much load can a 100 amp circuit carry?

SystemAt 100 AAt 80 A
120 V single phase12.0 kW9.6 kW
240 V single phase (120/240 V)24.0 kW19.2 kW
208 V three phase (120/208 V)36.0 kW28.8 kW
600 V three phase (347/600 V)103.9 kW83.1 kW

The figures assume a balanced load and unity power factor. A 100 A service at 240 V is 24 kW, which is exactly the Rule 8-200 minimum load for a dwelling of 80 m² or more. Continuous loads on breakers not marked for 100% continuous operation are generally limited to 80% of the rating under Rule 8-104. The amps to watts calculator handles power factor.

CEC vs NEC for 100 amps

The raw ampacities in CEC Tables 2 and 4 match NEC Table 310.16 for these sizes, so the basic answer (3 AWG copper, 1 AWG aluminum) is the same in both countries. The differences: Canada has no 83% dwelling service rule, voltage drop is mandatory under Rule 8-102 rather than an informational note, run lengths and the code itself are in metres, bonding conductors come from Table 16 instead of NEC Table 250.122 (same 8 AWG Cu / 6 AWG Al at 100 A), and provinces adopt different editions: CSA C22.1:24 in Alberta and Saskatchewan, the 2024 Ontario Electrical Safety Code in Ontario, the BC Electrical Code 2024 in British Columbia, and CSA C22.1:21 with amendments in Quebec. For the US version of this page, see wire size for 100 amps (NEC).

Sources

Frequently asked questions

What size wire for 100 amps in Canada?

3 AWG copper (CEC Table 2, 100 A at 75 °C) or 1 AWG aluminum (Table 4, 100 A at 75 °C), where the breaker, panel and conductor are all rated for 75 °C. If the equipment is limited to 60 °C, copper goes up to 1 AWG (110 A). Long runs may need a larger size to meet the Rule 8-102 voltage drop limit.

What size wire for 100 amp service in Canada?

For a single dwelling, 3 AWG copper or 1 AWG aluminum at 75 °C. Canada has no equivalent of the NEC 310.12 83% rule, so a 100 A service does not drop to 4 AWG copper or 2 AWG aluminum. Rule 8-200 sets 100 A as the minimum service for a single dwelling with 80 m² or more of floor area, excluding the basement (60 A below 80 m²).

What size wire for a 100 amp subpanel in Canada?

The same ampacity starting point: 3 AWG copper or 1 AWG aluminum with 75 °C terminations at both ends, plus a neutral if 120 V loads are supplied and an 8 AWG copper or 6 AWG aluminum bonding conductor (Table 16). On a 240 V feeder sized with the Rule 8-102 default of 80 A, 3 AWG copper reaches about 55 m before the drop passes 3%.

Can I use 2 AWG aluminum on a 100 amp breaker in Canada?

2 AWG aluminum is rated 90 A in the 75 °C column of CEC Table 4, which is below 100 A, so it does not meet the ampacity for a 100 A feeder or service. Use 1 AWG aluminum (100 A) or larger.

What load do I use for voltage drop on a 100 A feeder in Canada?

Rule 8-102 says to calculate voltage drop on the connected load of the feeder or branch circuit if it is known, or otherwise on 80% of the rating of the overcurrent device. For a 100 A breaker with unknown load, that is 80 A. The limits are 3% for the feeder or branch circuit and 5% total from the supply side of the consumer's service to the point of use.

What size bonding wire for a 100 amp subpanel in Canada?

8 AWG copper or 6 AWG aluminum, from CEC Table 16 for an overcurrent device up to 100 A (Rule 10-616). If the circuit conductors are made larger to compensate for voltage drop, the bonding conductor is sized from the ampacity of the largest ungrounded conductor instead, which can push it to 6 AWG copper.

Does a 90 °C cable let me use smaller wire for 100 amps?

Usually not. Rule 4-006 limits the conductor to the termination temperature of the equipment. Unmarked equipment rated 100 A or less is treated as 60 °C and most breakers and panelboards are marked 75 °C, so 3 AWG copper T90 or TECK90 is used at its 100 A (75 °C) rating, not its 115 A (90 °C) rating, at least for the first 1.2 m from the termination.

Related calculators, charts and guides