What Size Wire for 60 Amps?

6 AWG copper or 4 AWG aluminum for a 60 A circuit or feeder (NEC Table 310.16, 75 °C column). Below: the NM cable and 6/3 Romex question, EV chargers, wire size by distance, how far each size can run at 240 V and three phase, and the ground and conduit size.

Quick answer: wire size for a 60 amp breaker

Minimum conductor whose table ampacity is at least 60 A, with not more than three current-carrying conductors at 30 °C (86 °F) ambient.

Wire and terminal ratingMinimum sizeTable ampacity
Copper, 60 °C column (NM cable, unmarked terminals)4 AWG70 A
Copper, 75 °C column (THHN/THWN-2, 75 °C terminals)6 AWG65 A
Aluminum, 60 °C column3 AWG65 A
Aluminum, 75 °C column (XHHW-2, SER, 75 °C terminals)4 AWG65 A

NEC 110.14(C)(1)(a) limits circuits of 100 A or less to the 60 °C column unless the equipment is listed and marked for 75 °C, which most current breakers and panels are. The 90 °C column (75 A for 6 AWG copper) is only a starting point for derating.

6 AWG NM cable on a 60 amp breaker

6/3 or 6/2 NM-B is the most common question at this size. NM cable must use the 60 °C column (NEC 334.80), so 6 AWG copper NM-B is rated 55 A. Because 55 A is not a standard breaker size, NEC 240.4(B) allows the next size up, 60 A, when all three conditions hold:

The calculated load still has to fit the 55 A conductor. A continuous load needs conductors rated at 125% of it (NEC 210.19(A)(1) and 215.2(A)(1)), so 6 AWG NM-B tops out at a continuous load of 44 A. For a full 60 A of conductor ampacity in NM cable, use 4 AWG (70 A).

Wire size for a 60 amp EV charger

Charger outputBreaker (125%)Copper THHN, 75 °CCopper NM-B, 60 °C
32 A40 A8 AWG (50 A)8 AWG (40 A)
40 A50 A8 AWG (50 A)6 AWG (55 A)
48 A60 A6 AWG (65 A)4 AWG (70 A)

EV supply equipment is a continuous load, so NEC 625.41 sizes the breaker at 125% of the charger's rating and 210.19(A)(1) sizes the conductors the same way. A 48 A wall charger therefore needs a 60 A breaker and conductors rated at least 60 A. Most hardwired chargers need two hots and a ground, no neutral. Follow the charger's manual for the allowed conductor material and terminal temperature.

Wire size for 60 amps by distance (240 V)

Smallest size that keeps a 120/240 V single-phase run at or under a 3% voltage drop. The 48 A columns are for a continuous load on a 60 A breaker, such as an EV charger. Ampacity sets the floor, so the table never goes below 6 AWG copper or 4 AWG aluminum.

One-way run length. 3% drop at 240 V, NEC Chapter 9 Table 8 resistance at 75 °C.
RunCu, 60 ACu, 48 AAl, 60 AAl, 48 A
50 ft6 AWG6 AWG4 AWG4 AWG
75 ft6 AWG6 AWG4 AWG4 AWG
100 ft6 AWG6 AWG4 AWG4 AWG
125 ft4 AWG6 AWG3 AWG4 AWG
150 ft4 AWG6 AWG2 AWG3 AWG
200 ft3 AWG4 AWG1 AWG2 AWG
250 ft2 AWG3 AWG1/0 AWG1 AWG
300 ft2 AWG3 AWG2/0 AWG1/0 AWG

Example: a 48 A EV charger in a detached garage 200 ft from the panel. 6 AWG copper reaches 152 ft at 48 A, so the run needs 4 AWG copper, which reaches 243 ft. The ground must then be upsized too (see ground).

Maximum length at 60 amps by wire size

The longest one-way run, in feet, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are DC resistance figures.

Copper

Size240 V, 3%240 V at 48 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
6 AWG122152203122282
4 AWG194243324194449
3 AWG244306408245565
2 AWG309386515309714
1 AWG389487649389899
1/0 AWG4916148194921135
2/0 AWG62077510346201432

Aluminum

Size240 V, 3%240 V at 48 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
4 AWG118147196118272
3 AWG148186248148343
2 AWG188235313188434
1 AWG237296395237547
1/0 AWG298373497298689
2/0 AWG377471628377871
3/0 AWG4765957934761099
4/0 AWG59974910006001385

Formulas: single phase L = %·V·1000 / (2·I·R), three phase L = %·V·1000 / (√3·I·R), with R in ohms per 1000 ft. NEC 215.2(A)(1) Informational Note 2 recommends 3% on a feeder and 5% total. Use the voltage drop calculator for your exact load.

Ground wire for 60 amps

Conduit size for 60 amp wire

Smallest conduit at 40% fill (NEC Chapter 9 Table 1) using THHN/THWN-2 areas from Chapter 9 Table 5.

RunConductorsArea, in²EMTPVC 40
Subpanel feeder, copper 75 °C (2 hots + neutral)3 × 6 AWG + 10 AWG0.1733/43/4
Subpanel feeder, aluminum 75 °C (2 hots + neutral)3 × 4 AWG + 8 AWG0.28411
240 V EV charger or other 2-wire load, copper2 × 6 AWG + 10 AWG0.1223/43/4
Feeder upsized for 200 ft, copper3 × 4 AWG + 6 AWG0.29811

XHHW-2 aluminum areas differ slightly from THHN, so check the conduit fill calculator for your insulation.

How much load can a 60 amp circuit carry?

SystemAt 60 AContinuous (48 A)
120 V single phase7.2 kW5.8 kW
240 V single phase14.4 kW11.5 kW
208 V three phase21.6 kW17.3 kW
480 V three phase49.9 kW39.9 kW
600 V three phase62.4 kW49.9 kW

Balanced load, unity power factor. The amps to watts calculator handles power factor.

When more than three wires share a conduit

With four to six current-carrying conductors in one raceway, NEC 310.15(C)(1) cuts ampacity to 80%. From the 90 °C column, 6 AWG copper drops to 60 A, which still covers 60 A as long as the 75 °C terminal rating (65 A) is also met. At seven to nine conductors (70%) it falls to 52 A, so upsize to 4 AWG (66 A). See wire derating.

In Canada

CEC Table 2 (copper) and Table 4 (aluminum) give the same ampacities for these sizes, so 6 AWG copper or 4 AWG aluminum carries 60 A at 75 °C. Rule 8-102 makes the 3% and 5% voltage drop limits mandatory, and distances are in metres. Use the Canadian wire size calculator or see CEC Table 2.

For larger circuits, see wire size for 100 amps and wire size for 200 amps.

This page is a quick reference. Confirm against the code edition your jurisdiction has adopted, the equipment markings and your inspector.

Frequently asked questions

What size wire for 60 amps?

6 AWG copper or 4 AWG aluminum, using the 75 °C column of NEC Table 310.16 (both rated 65 A). If the terminals or cable are limited to 60 °C, such as NM cable, the full-ampacity answer is 4 AWG copper (70 A) or 3 AWG aluminum (65 A).

Can I use 6/3 NM-B (Romex) on a 60 amp breaker?

Sometimes. 6 AWG NM-B is held to the 60 °C column by NEC 334.80, which is 55 A. NEC 240.4(B) lets a 55 A conductor go on the next standard breaker size, 60 A, when it does not feed a multioutlet branch circuit for cord-and-plug loads and the calculated load is 55 A or less. It does not work for a 48 A continuous load such as an EV charger, because 125% of 48 A is 60 A, more than 55 A. In that case use 4 AWG NM-B or 6 AWG THHN in conduit.

What size wire for a 60 amp EV charger?

A charger that draws 48 A is a continuous load, so the circuit needs a 60 A breaker and conductors rated at least 60 A (NEC 625.41 and 210.19(A)(1)). That is 6 AWG copper THHN/THWN-2 with 75 °C terminals (65 A) or 4 AWG copper NM-B (70 A). Check the charger's installation manual; many only accept copper.

What size wire for a 60 amp subpanel?

Four wires of 6 AWG copper or 4 AWG aluminum (two hots, an insulated neutral) plus a 10 AWG copper or 8 AWG aluminum equipment ground, with 75 °C terminals at both ends. Past about 100 ft, check voltage drop with the distance table on this page.

How far can you run 6 AWG copper at 60 amps?

About 122 ft one way at 240 V with a full 60 A load before drop passes 3%, or 152 ft at 48 A. At a 5% limit the full-load figure is 203 ft. These use the NEC Chapter 9 Table 8 resistance of 0.491 ohms per 1000 ft.

What size ground wire for 60 amps?

10 AWG copper or 8 AWG aluminum, from NEC Table 250.122 for a 60 A breaker. If the hot conductors are upsized for voltage drop, 250.122(B) requires the ground to be upsized by the same circular mil ratio.

What size conduit for 60 amp wire?

Three 6 AWG copper THHN and a 10 AWG copper ground fit in 3/4 inch EMT at 40% fill. The conduit table on this page shows the area math for aluminum and upsized runs.