What Size Wire for 50 Amps in Canada? (CEC)

8 AWG copper or 6 AWG aluminum for a 50 A circuit or subpanel under the Canadian Electrical Code (Table 2 and Table 4, 75 °C column), or 6 AWG copper and 4 AWG aluminum where terminations are limited to 60 °C. Below: why 8 AWG copper sits right on the line at 50 A, wire size by distance in metres under Rule 8-102, max run lengths at 120/240, 208 and 600 V, the Table 16 bonding conductor and how much load a 50 A circuit carries.

CEC data notice: CEC values were checked against public summaries of CSA C22.1:24, not the code book itself. Conduit and conductor areas use NEC Chapter 9 data, and some aluminum kcmil ampacities are unverified. Confirm against the CEC edition and provincial amendments adopted where you work.

Quick answer: wire size for a 50 A breaker in Canada

Minimum conductor for 50 A, not more than three conductors in a raceway or cable, 30 °C ambient.

Conductor and termination ratingMinimum sizeAmpacity
Copper, 75 °C (terminals marked 75 °C)8 AWG50 A (Table 2)
Copper, 60 °C (unmarked equipment rated 100 A or less)6 AWG55 A (Table 2)
Aluminum, 75 °C (terminals marked 75 °C)6 AWG50 A (Table 4)
Aluminum, 60 °C4 AWG55 A (Table 4)

Why 8 AWG copper is a borderline answer at 50 A

8 AWG copper is rated exactly 50 A in the 75 °C column of Table 2, with no margin, and 40 A in the 60 °C column. Rule 4-006 treats equipment rated 100 A or less that is not marked with a termination temperature as 60 °C, so if the breaker, the panel or the equipment at the far end (a range, EV charger, welder receptacle or hot tub disconnect) is unmarked, the minimum becomes 6 AWG copper. Any derating for more than three conductors (Table 5C) or a hot location (Table 5A) also pushes 8 AWG below 50 A, because there is no headroom left.

CEC Table 2 (copper) and Table 4 (aluminum), not more than three conductors, 30 °C ambient.
SizeCu 60 °CCu 75 °CCu 90 °CAl 60 °CAl 75 °CAl 90 °C
10 AWG30 A35 A40 A———
8 AWG40 A50 A55 A35 A40 A45 A
6 AWG55 A65 A75 A40 A50 A55 A
4 AWG70 A85 A95 A55 A65 A75 A

The 90 °C rating of T90 or TECK90 (55 A for 8 AWG copper) does not raise the circuit rating: the conductor is used at the termination column, at least for the first 1.2 m from the termination. The 90 °C value is the starting point for correction factors, covered on the CEC Table 2 chart.

Wire size for 50 amps by distance (metres, 240 V)

Smallest size that keeps a 120/240 V single-phase run at or under the Rule 8-102 3% limit. The 40 A columns use the Rule 8-102 default for an unknown load (80% of a 50 A breaker); the 50 A columns are for a known full load. The table starts at the 75 °C minimum (8 AWG copper, 6 AWG aluminum).

One-way run length. 3% drop (7.2 V) at 240 V, conductor resistance at 75 °C.
RunCu, 40 ACu, 50 AAl, 40 AAl, 50 A
10 m8 AWG8 AWG6 AWG6 AWG
15 m8 AWG8 AWG6 AWG6 AWG
20 m8 AWG8 AWG6 AWG6 AWG
25 m8 AWG8 AWG6 AWG6 AWG
30 m8 AWG6 AWG6 AWG4 AWG
40 m6 AWG6 AWG4 AWG4 AWG
50 m6 AWG4 AWG4 AWG3 AWG
60 m4 AWG4 AWG3 AWG2 AWG
75 m4 AWG3 AWG2 AWG1 AWG

If your terminations are limited to 60 °C, start at 6 AWG copper or 4 AWG aluminum instead:

60 °C terminations, 40 A load, 3% at 240 V.
RunCopperAluminum
30 m6 AWG4 AWG
50 m6 AWG4 AWG
60 m4 AWG3 AWG
75 m4 AWG2 AWG
90 m3 AWG1 AWG
110 m3 AWG1/0 AWG

Example: a 50 A subpanel in a garage 25 m from the main panel, load not yet known. Rule 8-102 says to use 40 A. 8 AWG copper reaches 35 m at 40 A and 6 AWG copper reaches 55 m. In aluminum, 6 AWG reaches 33 m and 4 AWG reaches 53 m. The 5% total limit includes the service conductors and the branch circuits after the subpanel, so leave room for them.

Maximum length at 50 amps by wire size

The longest one-way run, in metres, before each size reaches the drop shown. Three-phase columns use the √3 formula and are resistance-only figures.

Copper

Size240 V, 40 A, 3%240 V, 50 A, 3%240 V, 40 A, 5%208 V 3-ph, 40 A, 3%600 V 3-ph, 40 A, 3%
8 AWG35285935103
6 AWG55449355161
4 AWG897114889257
3 AWG11189186112323
2 AWG141113235141408
1 AWG178142296178514
1/0 AWG224179374225649

Aluminum

Size240 V, 40 A, 3%240 V, 50 A, 3%240 V, 40 A, 5%208 V 3-ph, 40 A, 3%600 V 3-ph, 40 A, 3%
6 AWG3327563398
4 AWG53439054155
3 AWG685411368196
2 AWG856814386248
1 AWG10886180108313
1/0 AWG136109227136393
2/0 AWG172138287172498

For your exact load and length, use the Canadian voltage drop calculator or the Canadian wire size calculator, which checks ampacity and Rule 8-102 together.

Bonding conductor for 50 amps

How much load can a 50 amp circuit carry?

SystemAt 50 AAt 40 A (80%)
120 V single phase6.0 kW4.8 kW
240 V single phase (120/240 V)12.0 kW9.6 kW
208 V three phase (120/208 V)18.0 kW14.4 kW
600 V three phase (347/600 V)52.0 kW41.6 kW

Balanced load, unity power factor. Rule 8-104 limits a continuous load on a breaker not marked for 100% continuous operation to 80% of its rating, which is 40 A on a 50 A breaker. The amps to watts calculator handles power factor.

Common 50 A circuits in Canadian homes

CEC vs NEC for 50 amps

The raw ampacities in CEC Tables 2 and 4 match NEC Table 310.16 for these sizes, so the 75 °C answer (8 AWG copper, 6 AWG aluminum) is the same in both countries. The differences: voltage drop is mandatory in Canada under Rule 8-102 instead of an informational note, the code works in metres, bonding conductors come from Table 16 instead of NEC Table 250.122 (both give 10 AWG Cu / 8 AWG Al at 50 A), and provinces adopt different editions of the code. For the US version, with NM-B cable, 14-50 receptacle and range tables, see wire size for 50 amps (NEC). For larger Canadian circuits, see 60 amps and 100 amps.

Sources

Frequently asked questions

What size wire for 50 amps in Canada?

8 AWG copper (CEC Table 2, 50 A at 75 °C) or 6 AWG aluminum (Table 4, 50 A at 75 °C), but only where the breaker and the equipment at both ends are marked for 75 °C. With unmarked or 60 °C equipment, use 6 AWG copper (55 A) or 4 AWG aluminum (55 A). Runs longer than about 35 m in 8 AWG copper at 240 V need a larger size to stay within the Rule 8-102 3% limit.

Is 8 AWG copper good for 50 amps in Canada?

Only in the 75 °C column of Table 2, where it is exactly 50 A. In the 60 °C column it is 40 A. Rule 4-006 treats equipment rated 100 A or less that is not marked with a termination temperature as 60 °C, so 8 AWG copper on a 50 A breaker depends on the markings on the breaker and the load equipment.

Is 6 AWG copper overkill for a 50 amp circuit?

No. It is the size you need when terminations are limited to 60 °C (55 A in Table 2), and it is also the usual upsize for voltage drop: at the Rule 8-102 default of 40 A on 240 V, 6 AWG copper reaches about 55 m before passing 3%, against about 35 m for 8 AWG.

What size wire for a 50 amp subpanel in Canada?

The same as any 50 A feeder: 8 AWG copper or 6 AWG aluminum with 75 °C terminations (6 Cu / 4 Al at 60 °C), a neutral if 120 V loads are supplied, and a bonding conductor of at least 10 AWG copper or 8 AWG aluminum from Table 16. Size up for distance using the tables on this page.

What load do I use for voltage drop on a 50 A circuit in Canada?

Rule 8-102 uses the connected load when it is known, otherwise 80% of the overcurrent device rating, which is 40 A for a 50 A breaker. The limits are 3% for a feeder or branch circuit and 5% total from the supply side of the consumer's service to the point of use.

What size bonding wire for a 50 amp circuit in Canada?

10 AWG copper or 8 AWG aluminum, from the CEC Table 16 row for overcurrent devices rated over 30 A up to 60 A (Rule 10-616). A 30 A circuit needs 12 AWG copper or 10 AWG aluminum.

How much can a 50 amp breaker carry continuously?

Under Rule 8-104, a continuous load on a breaker not marked for 100% continuous operation is limited to 80% of its rating, which is 40 A on a 50 A breaker (9.6 kW at 240 V). That is why a 40 A Level 2 EV charger is usually installed on a 50 A circuit.