Quick answer: wire size for a 50 A breaker in Canada
Minimum conductor for 50 A, not more than three conductors in a raceway or cable, 30 °C ambient.
| Conductor and termination rating | Minimum size | Ampacity |
|---|---|---|
| Copper, 75 °C (terminals marked 75 °C) | 8 AWG | 50 A (Table 2) |
| Copper, 60 °C (unmarked equipment rated 100 A or less) | 6 AWG | 55 A (Table 2) |
| Aluminum, 75 °C (terminals marked 75 °C) | 6 AWG | 50 A (Table 4) |
| Aluminum, 60 °C | 4 AWG | 55 A (Table 4) |
Why 8 AWG copper is a borderline answer at 50 A
8 AWG copper is rated exactly 50 A in the 75 °C column of Table 2, with no margin, and 40 A in the 60 °C column. Rule 4-006 treats equipment rated 100 A or less that is not marked with a termination temperature as 60 °C, so if the breaker, the panel or the equipment at the far end (a range, EV charger, welder receptacle or hot tub disconnect) is unmarked, the minimum becomes 6 AWG copper. Any derating for more than three conductors (Table 5C) or a hot location (Table 5A) also pushes 8 AWG below 50 A, because there is no headroom left.
| Size | Cu 60 °C | Cu 75 °C | Cu 90 °C | Al 60 °C | Al 75 °C | Al 90 °C |
|---|---|---|---|---|---|---|
| 10 AWG | 30 A | 35 A | 40 A | — | — | — |
| 8 AWG | 40 A | 50 A | 55 A | 35 A | 40 A | 45 A |
| 6 AWG | 55 A | 65 A | 75 A | 40 A | 50 A | 55 A |
| 4 AWG | 70 A | 85 A | 95 A | 55 A | 65 A | 75 A |
The 90 °C rating of T90 or TECK90 (55 A for 8 AWG copper) does not raise the circuit rating: the conductor is used at the termination column, at least for the first 1.2 m from the termination. The 90 °C value is the starting point for correction factors, covered on the CEC Table 2 chart.
Wire size for 50 amps by distance (metres, 240 V)
Smallest size that keeps a 120/240 V single-phase run at or under the Rule 8-102 3% limit. The 40 A columns use the Rule 8-102 default for an unknown load (80% of a 50 A breaker); the 50 A columns are for a known full load. The table starts at the 75 °C minimum (8 AWG copper, 6 AWG aluminum).
| Run | Cu, 40 A | Cu, 50 A | Al, 40 A | Al, 50 A |
|---|---|---|---|---|
| 10 m | 8 AWG | 8 AWG | 6 AWG | 6 AWG |
| 15 m | 8 AWG | 8 AWG | 6 AWG | 6 AWG |
| 20 m | 8 AWG | 8 AWG | 6 AWG | 6 AWG |
| 25 m | 8 AWG | 8 AWG | 6 AWG | 6 AWG |
| 30 m | 8 AWG | 6 AWG | 6 AWG | 4 AWG |
| 40 m | 6 AWG | 6 AWG | 4 AWG | 4 AWG |
| 50 m | 6 AWG | 4 AWG | 4 AWG | 3 AWG |
| 60 m | 4 AWG | 4 AWG | 3 AWG | 2 AWG |
| 75 m | 4 AWG | 3 AWG | 2 AWG | 1 AWG |
If your terminations are limited to 60 °C, start at 6 AWG copper or 4 AWG aluminum instead:
| Run | Copper | Aluminum |
|---|---|---|
| 30 m | 6 AWG | 4 AWG |
| 50 m | 6 AWG | 4 AWG |
| 60 m | 4 AWG | 3 AWG |
| 75 m | 4 AWG | 2 AWG |
| 90 m | 3 AWG | 1 AWG |
| 110 m | 3 AWG | 1/0 AWG |
Example: a 50 A subpanel in a garage 25 m from the main panel, load not yet known. Rule 8-102 says to use 40 A. 8 AWG copper reaches 35 m at 40 A and 6 AWG copper reaches 55 m. In aluminum, 6 AWG reaches 33 m and 4 AWG reaches 53 m. The 5% total limit includes the service conductors and the branch circuits after the subpanel, so leave room for them.
Maximum length at 50 amps by wire size
The longest one-way run, in metres, before each size reaches the drop shown. Three-phase columns use the √3 formula and are resistance-only figures.
Copper
| Size | 240 V, 40 A, 3% | 240 V, 50 A, 3% | 240 V, 40 A, 5% | 208 V 3-ph, 40 A, 3% | 600 V 3-ph, 40 A, 3% |
|---|---|---|---|---|---|
| 8 AWG | 35 | 28 | 59 | 35 | 103 |
| 6 AWG | 55 | 44 | 93 | 55 | 161 |
| 4 AWG | 89 | 71 | 148 | 89 | 257 |
| 3 AWG | 111 | 89 | 186 | 112 | 323 |
| 2 AWG | 141 | 113 | 235 | 141 | 408 |
| 1 AWG | 178 | 142 | 296 | 178 | 514 |
| 1/0 AWG | 224 | 179 | 374 | 225 | 649 |
Aluminum
| Size | 240 V, 40 A, 3% | 240 V, 50 A, 3% | 240 V, 40 A, 5% | 208 V 3-ph, 40 A, 3% | 600 V 3-ph, 40 A, 3% |
|---|---|---|---|---|---|
| 6 AWG | 33 | 27 | 56 | 33 | 98 |
| 4 AWG | 53 | 43 | 90 | 54 | 155 |
| 3 AWG | 68 | 54 | 113 | 68 | 196 |
| 2 AWG | 85 | 68 | 143 | 86 | 248 |
| 1 AWG | 108 | 86 | 180 | 108 | 313 |
| 1/0 AWG | 136 | 109 | 227 | 136 | 393 |
| 2/0 AWG | 172 | 138 | 287 | 172 | 498 |
For your exact load and length, use the Canadian voltage drop calculator or the Canadian wire size calculator, which checks ampacity and Rule 8-102 together.
Bonding conductor for 50 amps
- Bonding conductor (Table 16, Rule 10-616): 10 AWG copper or 8 AWG aluminum for an overcurrent device rated over 30 A up to 60 A, which covers 50 A.
- Neighbouring rows: devices up to 30 A need 12 AWG copper or 10 AWG aluminum; devices up to 100 A need 8 AWG copper or 6 AWG aluminum.
- Upsized conductors: if you upsize the circuit conductors for voltage drop, confirm with your inspector whether the bonding conductor must be increased under the edition adopted in your province.
How much load can a 50 amp circuit carry?
| System | At 50 A | At 40 A (80%) |
|---|---|---|
| 120 V single phase | 6.0 kW | 4.8 kW |
| 240 V single phase (120/240 V) | 12.0 kW | 9.6 kW |
| 208 V three phase (120/208 V) | 18.0 kW | 14.4 kW |
| 600 V three phase (347/600 V) | 52.0 kW | 41.6 kW |
Balanced load, unity power factor. Rule 8-104 limits a continuous load on a breaker not marked for 100% continuous operation to 80% of its rating, which is 40 A on a 50 A breaker. The amps to watts calculator handles power factor.
Common 50 A circuits in Canadian homes
- Level 2 EV charger: a charger set to 40 A output is a continuous load, so it needs a 50 A circuit under the 80% limit. Many chargers can be set lower (32 A on a 40 A circuit) if the panel calculation is tight.
- Electric range: ranges are commonly on a 40 A or 50 A circuit; follow the range nameplate and installation instructions for the breaker size, then size the wire from the table above.
- Subpanel in a garage or shop: a 50 A feeder at 240 V gives 12 kW; size up for the run length using the distance tables.
CEC vs NEC for 50 amps
The raw ampacities in CEC Tables 2 and 4 match NEC Table 310.16 for these sizes, so the 75 °C answer (8 AWG copper, 6 AWG aluminum) is the same in both countries. The differences: voltage drop is mandatory in Canada under Rule 8-102 instead of an informational note, the code works in metres, bonding conductors come from Table 16 instead of NEC Table 250.122 (both give 10 AWG Cu / 8 AWG Al at 50 A), and provinces adopt different editions of the code. For the US version, with NM-B cable, 14-50 receptacle and range tables, see wire size for 50 amps (NEC). For larger Canadian circuits, see 60 amps and 100 amps.
Sources
- VRI Electrical, Cable Ampacity Tables – CEC / CSA C22.1 (Tables 2 and 4)
- CSA Group, CEC Section 8 excerpt (Rules 8-102, 8-104)
- Electrical Industry News Week, Guide to the CE Code, Section 4 (Rule 4-006)
- IAEI Magazine, Application of Rule 4-006
- Hongbin Li, Bonding conductor size, CSA C22.1:24 Table 16
- Conductor resistance: NEC Chapter 9 Table 8 values at 75 °C, converted to metres