What Size Wire for 50 Amps?

8 AWG copper or 6 AWG aluminum for a 50 A circuit with 75 °C terminals, or 6 AWG copper in NM cable (NEC Table 310.16). Below: why 8 AWG Romex fails, EV chargers and 14-50 outlets, ranges, wire size by distance, how far each size can run at 240 V and three phase, and the ground and conduit size.

Quick answer: wire size for a 50 amp breaker

Minimum conductor whose table ampacity is at least 50 A, with not more than three current-carrying conductors at 30 °C (86 °F) ambient.

Wire and terminal ratingMinimum sizeTable ampacity
Copper, 60 °C column (NM cable, unmarked terminals)6 AWG55 A
Copper, 75 °C column (THHN/THWN-2, 75 °C terminals)8 AWG50 A
Aluminum, 60 °C column4 AWG55 A
Aluminum, 75 °C column (XHHW-2, SER, 75 °C terminals)6 AWG50 A

NEC 110.14(C)(1)(a) limits circuits of 100 A or less to the 60 °C column unless the equipment is listed and marked for 75 °C, which most current breakers and panels are. Both ends of the circuit count: if a receptacle, range terminal block or appliance is marked 60 °C, use the 60 °C sizes. The 90 °C column (55 A for 8 AWG copper) is only a starting point for derating.

NM cable (Romex) on a 50 amp breaker

NM-B must use the 60 °C column (NEC 334.80), so the sizes that look right in the 75 °C column do not work in NM cable:

NM-B copper size60 °C ampacityOn a 50 A breaker?
8 AWG (8/2, 8/3)40 ANo: 40 A is a standard breaker size, so 240.4(B) does not apply
6 AWG (6/2, 6/3)55 AYes

NEC 240.4(B) lets a conductor go on the next standard breaker size only when its ampacity is not itself a standard rating. 40 A is in the 240.6(A) list, so 8 AWG NM-B is a 40 A cable, full stop. This is the most common mistake at 50 A.

Wire size for a 50 amp EV charger or NEMA 14-50 outlet

Charger outputBreaker (125%)Copper THHN, 75 °CCopper NM-B, 60 °C
24 A30 A10 AWG (35 A)10 AWG (30 A)
32 A40 A8 AWG (50 A)8 AWG (40 A)
40 A50 A8 AWG (50 A)6 AWG (55 A)

EV supply equipment is a continuous load, so NEC 625.41 sizes the breaker at 125% of the charger's rating and 210.19(A)(1) sizes the conductors the same way. A charger set to 40 A therefore needs a 50 A breaker and conductors rated at least 50 A. A plug-in charger on a NEMA 14-50 receptacle uses four wires (two hots, neutral, ground), and NEC Table 210.21(B)(3) allows a 50 A receptacle on a 40 A or 50 A circuit. Check the charger manual for its maximum setting on a 14-50 plug.

Wire size for a 50 amp range, cooktop or oven

NEC 210.19(A)(3) sets the minimum branch-circuit rating for a household range of 8¾ kW or more at 40 A, and Table 220.55 gives the demand load used to size it. Many ranges list a 40 A or 50 A circuit on the nameplate; follow the nameplate. For a 50 A range circuit:

New range circuits need a separate insulated neutral and equipment ground (four-wire). The older three-wire connection using the neutral as the ground is only allowed to stay on existing branch circuits (NEC 250.140 exception).

Wire size for 50 amps by distance (240 V)

Smallest size that keeps a 120/240 V single-phase run at or under a 3% voltage drop. The 40 A columns are for a continuous load on a 50 A breaker, such as an EV charger. Ampacity sets the floor, so the table never goes below 8 AWG copper or 6 AWG aluminum (75 °C).

One-way run length. 3% drop at 240 V, NEC Chapter 9 Table 8 resistance at 75 °C.
RunCu, 50 ACu, 40 AAl, 50 AAl, 40 A
50 ft8 AWG8 AWG6 AWG6 AWG
75 ft8 AWG8 AWG6 AWG6 AWG
100 ft6 AWG8 AWG4 AWG6 AWG
125 ft6 AWG6 AWG4 AWG4 AWG
150 ft4 AWG6 AWG3 AWG4 AWG
200 ft4 AWG4 AWG2 AWG3 AWG
250 ft3 AWG4 AWG1 AWG2 AWG
300 ft2 AWG3 AWG1/0 AWG1 AWG

Example: a 40 A EV charger in a detached garage 150 ft from the panel. 8 AWG copper reaches 117 ft at 40 A, so the run needs 6 AWG copper, which reaches 183 ft. The ground must then be upsized too (see ground).

Maximum length at 50 amps by wire size

The longest one-way run, in feet, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are DC resistance figures.

Copper

Size240 V, 3%240 V at 40 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
8 AWG9411715794217
6 AWG146183244146338
4 AWG233292389233539
3 AWG293367489294678
2 AWG371463618371857
1 AWG4675847794671079
1/0 AWG5907379835901362

Aluminum

Size240 V, 3%240 V at 40 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
6 AWG8911114889205
4 AWG141177236141327
3 AWG178223297178412
2 AWG225282376225521
1 AWG284355474284657
1/0 AWG358447597358827
2/0 AWG4525667544531045
3/0 AWG5717149525711319

Formulas: single phase L = %·V·1000 / (2·I·R), three phase L = %·V·1000 / (√3·I·R), with R in ohms per 1000 ft. The NEC informational notes in 210.19 and 215.2 recommend 3% on a branch circuit or feeder and 5% total. Use the voltage drop calculator for your exact load.

Ground wire for 50 amps

Conduit size for 50 amp wire

Smallest conduit at 40% fill (NEC Chapter 9 Table 1) using THHN/THWN-2 areas from Chapter 9 Table 5.

RunConductorsArea, in²EMTPVC 40
Range or subpanel feeder, copper 75 °C (2 hots + neutral)3 × 8 AWG + 10 AWG0.1313/43/4
Subpanel feeder, aluminum 75 °C (2 hots + neutral)3 × 6 AWG + 8 AWG0.1893/43/4
240 V EV charger, welder or other 2-wire load, copper2 × 8 AWG + 10 AWG0.0941/21/2
Feeder upsized for 150 ft, copper3 × 6 AWG + 8 AWG0.1893/43/4

XHHW-2 aluminum areas differ slightly from THHN, so check the conduit fill calculator for your insulation.

How much load can a 50 amp circuit carry?

SystemAt 50 AContinuous (40 A)
120 V single phase6.0 kW4.8 kW
240 V single phase12.0 kW9.6 kW
208 V three phase18.0 kW14.4 kW
480 V three phase41.6 kW33.3 kW
600 V three phase52.0 kW41.6 kW

Balanced load, unity power factor. The amps to watts calculator handles power factor.

When more than three wires share a conduit

With four to six current-carrying conductors in one raceway, NEC 310.15(C)(1) cuts ampacity to 80%. From the 90 °C column, 8 AWG copper drops to 44 A, which is under 50 A, so upsize to 6 AWG (60 A). At seven to nine conductors (70%) 6 AWG gives 52 A, still enough. See wire derating.

In Canada

CEC Table 2 (copper) and Table 4 (aluminum) give the same ampacities for these sizes, so 8 AWG copper or 6 AWG aluminum carries 50 A at 75 °C. Rule 8-102 makes the 3% and 5% voltage drop limits mandatory, and distances are in metres. Use the Canadian wire size calculator or see CEC Table 2.

For larger circuits, see wire size for 60 amps, 100 amps and 200 amps.

This page is a quick reference. Confirm against the code edition your jurisdiction has adopted, the equipment markings and your inspector.

Frequently asked questions

What size wire for 50 amps?

8 AWG copper or 6 AWG aluminum, using the 75 °C column of NEC Table 310.16 (both rated 50 A). If the terminals or cable are limited to 60 °C, such as NM cable, use 6 AWG copper (55 A) or 4 AWG aluminum (55 A).

Can I use 8 AWG NM-B (Romex) on a 50 amp breaker?

No. NM cable is held to the 60 °C column by NEC 334.80, and 8 AWG copper is 40 A there. 40 A is itself a standard breaker size, so NEC 240.4(B) does not allow rounding up to 50 A. Use 6 AWG NM-B (55 A), or 8 AWG THHN in conduit with 75 °C terminals.

Is 6 AWG wire good for 50 amps?

Yes. 6 AWG copper is 55 A at 60 °C and 65 A at 75 °C, so it covers a 50 A breaker in NM cable or in conduit. 6 AWG aluminum is 50 A at 75 °C, enough only with 75 °C terminals.

What size wire for a 50 amp EV charger or NEMA 14-50 outlet?

A charger that draws 40 A is a continuous load, so NEC 625.41 and 210.19(A)(1) call for a 50 A breaker and conductors rated at least 50 A. That is 8 AWG copper THHN with 75 °C terminals (50 A) or 6 AWG copper NM-B (55 A). A 14-50 receptacle needs two hots, a neutral and a ground.

What size wire for a 50 amp range?

A 50 A range circuit is usually 6 AWG copper NM-B (55 A) or 8 AWG copper THHN in conduit at 75 °C (50 A), with an insulated neutral and an equipment ground. NEC 210.19(A)(3) sets a 40 A minimum branch-circuit rating for ranges of 8¾ kW or more.

How far can you run 8 AWG copper at 50 amps?

About 94 ft one way at 240 V with a full 50 A load before drop passes 3%, or 117 ft at 40 A. At a 5% limit the full-load figure is 157 ft. These use the NEC Chapter 9 Table 8 resistance of 0.764 ohms per 1000 ft for uncoated copper.

What size ground wire for 50 amps?

10 AWG copper or 8 AWG aluminum, from the 60 A row of NEC Table 250.122. If the hot conductors are upsized for voltage drop, 250.122(B) requires the ground to be upsized by the same circular mil ratio.