What Size Wire for 200 Amps in Canada? (CEC)

3/0 AWG copper or 250 kcmil aluminum for a 200 A service, feeder or subpanel under the Canadian Electrical Code (Tables 2 and 4, 75 °C column). Ontario still allows 2/0 copper or 4/0 aluminum on a single-dwelling service through Table 39. Below: the province-by-province answer, wire size by distance in metres under Rule 8-102, max run lengths at 120/240, 208 and 600 V, and Table 16 bonding and neutral sizes.

CEC data notice: CEC values were checked against public summaries of CSA C22.1:24, not the code book itself. Conduit and conductor areas use NEC Chapter 9 data, and some aluminum kcmil ampacities are unverified. Confirm against the CEC edition and provincial amendments adopted where you work.

Quick answer: wire size for a 200 A breaker in Canada

Minimum conductor for 200 A, not more than three conductors in a raceway or cable, 30 °C ambient.

Conductor and termination ratingMinimum sizeAmpacity
Copper, 75 °C (T90, RW90, TECK90 on 75 °C terminals)3/0 AWG200 A (Table 2)
Aluminum, 75 °C (ACWU90, RW90 on 75 °C terminals)250 kcmil205 A (Table 4)
Copper, 60 °C (equipment marked 60 °C only)250 kcmil215 A (Table 2)
Aluminum, 60 °C (equipment marked 60 °C only)350 kcmil210 A (Table 4)

Rule 4-006 limits the conductor to the termination temperature of the equipment. Unmarked equipment rated more than 100 A is treated as 75 °C, and 200 A panels, meter bases and breakers are normally marked 75 °C, so the 60 °C rows are rare at this size. A 90 °C conductor does not let you go smaller: 2/0 copper is 195 A at 90 °C but only 175 A at 75 °C, and 4/0 aluminum is 205 A at 90 °C but 180 A at 75 °C. The 90 °C value is the starting point for Table 5A and 5C correction factors.

200 amp service: national code vs Ontario Table 39

Table 39 used to give smaller sizes for single-dwelling services across Canada. It was deleted from CSA C22.1 in the 2021 edition. Ontario added it back as Rule 4-004 26) in its amendments (kept in the November 2024 Ontario amendments to CSA C22.1:24), so the answer for a house service depends on the province.

InstallationCopperAluminumBasis
Single-dwelling service, BC, Alberta, Saskatchewan and other provinces on CSA C22.1:21 or :243/0 AWG250 kcmilTables 2 and 4, 75 °C
Single-dwelling service or dwelling-unit feeder, Ontario (load ≤ 175 A Cu / 180 A Al)2/0 AWG4/0 AWGRule 4-004 26), Table 39, 90 °C insulation
Feeder to a subpanel, garage or shop (all provinces)3/0 AWG250 kcmilTables 2 and 4, 75 °C
Commercial or multi-unit main service3/0 AWG250 kcmilTables 2 and 4, 75 °C

Ontario's Table 39 (Ontario amendments, November 2024):

Overcurrent deviceCopper, 90 °CMax loadAluminum, 90 °CMax load
100 A3 AWG100 A2 AWG90 A
125 A2 AWG115 A1/0 AWG120 A
200 A2/0 AWG175 A4/0 AWG180 A
225 A3/0 AWG200 A250 kcmil205 A
400 A500 kcmil380 A700 kcmil375 A
400 A2 × 2/0350 A2 × 4/0360 A

Conditions: 3-wire 120/240 V or 120/208 V only, conductors with a 90 °C insulation rating, and the calculated or demonstrated load (Rules 8-104 and 8-106) must not exceed the 75 °C ampacity of the conductor. Loads calculated under Section 8 may exceed the table's maximum load by 5%. The max load column is the 75 °C ampacity, which is why it is lower than the breaker. British Columbia's regulator (Technical Safety BC bulletin IB-EL 2016-07, revised March 2025) works its 180 A example with Table 2 and lands on 3/0 copper. Quebec uses its own edition of the code; check with the authority having jurisdiction.

Wire size for 200 amps by distance (metres, 240 V)

Smallest size that keeps a 120/240 V single-phase run at or under the Rule 8-102 3% limit. The 160 A columns use the Rule 8-102 default for an unknown load (80% of a 200 A breaker); the 200 A columns are for a known full load. Ampacity sets the floor, so the table never goes below 3/0 copper or 250 kcmil aluminum.

One-way run length. 3% drop (7.2 V) at 240 V, conductor resistance at 75 °C.
RunCu, 160 ACu, 200 AAl, 160 AAl, 200 A
15 m3/0 AWG3/0 AWG250 kcmil250 kcmil
20 m3/0 AWG3/0 AWG250 kcmil250 kcmil
30 m3/0 AWG3/0 AWG250 kcmil250 kcmil
40 m3/0 AWG3/0 AWG250 kcmil250 kcmil
50 m3/0 AWG3/0 AWG250 kcmil250 kcmil
60 m3/0 AWG3/0 AWG250 kcmil250 kcmil
75 m3/0 AWG4/0 AWG250 kcmil300 kcmil
90 m4/0 AWG4/0 AWG300 kcmil350 kcmil
120 m250 kcmil300 kcmil400 kcmil500 kcmil

Example: a 200 A subpanel in a shop 100 m from the house, load not yet known. Rule 8-102 says to use 160 A. 3/0 copper reaches only 89 m, so it falls short; 4/0 copper (112 m) is the first size that works. In aluminum, 300 kcmil reaches 97 m and 350 kcmil (113 m) is needed. Upsizing also changes the bonding conductor when the new ampacity passes 200 A (see below), and the 5% total limit still includes the service conductors and the branch circuits after the subpanel.

Maximum length at 200 amps by wire size

The longest one-way run, in metres, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are resistance-only figures; large conductors in steel raceway at a low power factor see somewhat more drop from reactance.

Copper

Size240 V, 160 A, 3%240 V, 200 A, 3%240 V, 160 A, 5%208 V 3-ph, 160 A, 3%600 V 3-ph, 160 A, 3%
3/0 AWG897114989258
4/0 AWG11290187112325
250 kcmil133106221133384
300 kcmil159127266159461
350 kcmil186149311187539
400 kcmil213170356213616
500 kcmil265212443266767
600 kcmil320256534320925

Aluminum

Size240 V, 160 A, 3%240 V, 200 A, 3%240 V, 160 A, 5%208 V 3-ph, 160 A, 3%600 V 3-ph, 160 A, 3%
250 kcmil806413481233
300 kcmil977716197280
350 kcmil11390188113327
400 kcmil129103216129374
500 kcmil161129269161466
600 kcmil194155323194560
750 kcmil243194405243702

For your exact load and length, use the Canadian voltage drop calculator or the Canadian wire size calculator, which checks ampacity and Rule 8-102 together.

Bonding, grounding and neutral conductors for 200 amps

Copper circuit conductorTable 2 ampacity, 75 °CCopper bonding conductor (Table 16)
3/0 AWG200 A6 AWG
4/0 AWG230 A4 AWG
250 kcmil255 A4 AWG
300 kcmil285 A4 AWG
350 kcmil310 A3 AWG
400 kcmil335 A3 AWG

How much load can a 200 amp service carry?

SystemAt 200 AAt 160 A
240 V single phase (120/240 V)48.0 kW38.4 kW
208 V three phase (120/208 V)72.1 kW57.6 kW
600 V three phase (347/600 V)207.8 kW166.3 kW

The figures assume a balanced load and unity power factor. A 200 A service at 240 V is 48 kW. Rule 8-200 calculates a dwelling at 5,000 W for the first 90 m² of living area and 1,000 W for each extra 90 m², plus space heating, air conditioning, the range, tankless water heaters, EV charging and other loads at their demand factors; homes with electric heat or two EV chargers are the usual reason to go to 200 A. Continuous loads on breakers not marked for 100% continuous operation are generally limited to 80% of the rating under Rule 8-104. The amps to watts calculator handles power factor.

CEC vs NEC for 200 amps

The raw ampacities in CEC Tables 2 and 4 match NEC Table 310.16 for these sizes, so the feeder answer (3/0 copper, 250 kcmil aluminum) is the same in both countries. For a house service, the US uses NEC 310.12 (83% of the service rating, so 2/0 Cu or 4/0 Al at 200 A), which gives the same sizes as Ontario's Table 39 but not the national CEC. Other differences: voltage drop is mandatory under Rule 8-102, distances are in metres, and bonding comes from Table 16 instead of NEC Table 250.122 (both give 6 AWG Cu / 4 AWG Al at 200 A). For the US version, see wire size for 200 amps (NEC). For smaller Canadian services and feeders, see 100 amps, 60 amps and 50 amps.

Sources

Frequently asked questions

What size wire for 200 amps in Canada?

3/0 AWG copper (CEC Table 2, 200 A at 75 °C) or 250 kcmil aluminum (Table 4, 205 A at 75 °C), with 75 °C terminations. That is the national CSA C22.1 answer and the one British Columbia's safety regulator uses. Ontario keeps Table 39, which allows 2/0 copper or 4/0 aluminum for a single-dwelling service when the calculated load stays within the conductor's 75 °C ampacity.

Can I use 2/0 copper for a 200 amp service in Canada?

Only where Table 39 applies. Table 39 was removed from the national CSA C22.1 in the 2021 edition, but Ontario re-added it as Rule 4-004 26). In Ontario, 2/0 copper (90 °C insulation) is allowed on a 200 A single-dwelling service or dwelling-unit feeder if the calculated load does not exceed 175 A (the 75 °C ampacity), with loads permitted to exceed the table value by 5%. Elsewhere, 2/0 copper is rated 175 A at 75 °C, which is below 200 A.

Can I use 4/0 aluminum for 200 amps in Canada?

4/0 aluminum is rated 180 A in the 75 °C column of Table 4, so under the national code it does not meet a 200 A rating; use 250 kcmil aluminum (205 A). Ontario's Table 39 allows 4/0 aluminum on a 200 A single-dwelling service when the calculated load is no more than 180 A.

What size wire for a 200 amp subpanel 100 m away in Canada?

With the load unknown, Rule 8-102 uses 80% of the breaker rating, 160 A. At 240 V and 3% drop, 3/0 copper reaches about 89 m and 4/0 copper about 112 m, so a 100 m run needs 4/0 AWG copper or 350 kcmil aluminum. If the conductors are upsized, the bonding conductor is sized from the ampacity of the larger conductor.

What size bonding wire for a 200 amp subpanel in Canada?

6 AWG copper or 4 AWG aluminum, from CEC Table 16 for an overcurrent device or conductor ampacity up to 200 A. If the circuit conductors are made larger to compensate for voltage drop, Table 16 is entered with the ampacity of the largest ungrounded conductor, so upsizing 3/0 copper to 4/0 (230 A) or 250 kcmil (255 A) raises the bonding conductor to 4 AWG copper.

What size neutral for a 200 amp service in Ontario?

ESA Bulletin 4-3-11 shows the service neutral sized from Table 16 on the ampacity of the ungrounded conductors: with 2/0 copper (Table 39) or 3/0 copper, at least 6 AWG copper or 4 AWG aluminum; with 4/0 aluminum (Table 39), 4 AWG aluminum or 6 AWG copper; with 250 kcmil aluminum, 2 AWG aluminum or 4 AWG copper. The neutral must also carry the calculated unbalanced load and fit the equipment lugs.

Does a 200 amp service need a 200 amp load calculation in Canada?

No. Rule 8-200 gives the minimum service size for a single dwelling: the greater of the calculated load or 100 A (80 m² or more, excluding the basement) or 60 A (less than 80 m²). A 200 A service is a choice above that minimum, common with electric heat, heat pumps and EV charging. The conductors must still carry the rating of the main breaker unless a code rule such as Ontario's Table 39 says otherwise.

Related calculators, charts and guides