Quick answer: wire size for a 30 A breaker in Canada
Minimum conductor for 30 A, not more than three conductors in a raceway or cable, 30 °C ambient.
| Conductor | Minimum size | Why |
|---|---|---|
| Copper (any termination rating) | 10 AWG | 30 A at 60 °C (Table 2); Rule 14-104(2) allows 30 A |
| Aluminum, 60 °C or 75 °C | 8 AWG | 35 A at 60 °C (Table 4); 10 AWG Al is capped at 25 A |
| NMD90 cable (house wiring) | 10/2 or 10/3 | 10 AWG copper with a bare bond |
Because 10 AWG copper carries 30 A in the 60 °C column, the Rule 4-006 question that decides the 50 A and 60 A answers (are the terminals marked 75 °C?) does not change the copper size at 30 A.
Rule 14-104(2): why 12 AWG never goes on a 30 A breaker
Table 2 and Table 4 give the small sizes more ampacity than their breaker limits. Rule 14-104(2) caps the overcurrent protection for these conductors, so for 14 to 10 AWG the breaker cap, not the table, sets the answer.
| Size | 60 °C | 75 °C | 90 °C | Max breaker, Rule 14-104(2) |
|---|---|---|---|---|
| 14 AWG copper | 15 A | 20 A | 25 A | 15 A |
| 12 AWG copper | 20 A | 25 A | 30 A | 20 A |
| 10 AWG copper | 30 A | 35 A | 40 A | 30 A |
| 8 AWG copper | 40 A | 50 A | 55 A | Table ampacity |
| 12 AWG aluminum | 15 A | 20 A | 25 A | 15 A |
| 10 AWG aluminum | 25 A | 30 A | 35 A | 25 A |
| 8 AWG aluminum | 35 A | 40 A | 45 A | Table ampacity |
| 6 AWG aluminum | 40 A | 50 A | 55 A | Table ampacity |
The exceptions are rules that specifically allow a larger device for certain equipment, such as motors (Section 28) and electric heating (Rule 62-114). Table 13 (the next-standard-size permission in Rule 14-104(1)) does not override the small-conductor caps.
Common 30 A circuits in Canadian homes
Electric dryers
Most residential electric dryers are on a 30 A, 120/240 V circuit with a 14-30R receptacle, wired in 10/3 NMD90 (two hots, a neutral and the bare bond). Use the dryer's nameplate and installation instructions for the breaker size. A long run to a laundry room at the far end of the house is the case to check against the distance table below.
Electric storage-tank water heaters
Rule 62-402 sends storage-tank water heaters to the heating rules in Rule 62-114, which apply the continuous-load ratings of Rule 8-104. In practice the breaker is sized at 125% of the element current (the heater's full-load current), and the heater must be on a branch circuit that supplies nothing else. Common Canadian tank ratings at 240 V:
| Element | Current | 125% | Breaker | Copper |
|---|---|---|---|---|
| 3,000 W | 12.5 A | 15.6 A | 20 A | 12 AWG Cu |
| 3,800 W | 15.8 A | 19.8 A | 20 A | 12 AWG Cu |
| 4,500 W | 18.8 A | 23.4 A | 25 A | 10 AWG Cu |
| 5,500 W | 22.9 A | 28.6 A | 30 A | 10 AWG Cu |
A 3,000 W tank on a 20 A breaker with 12 AWG copper is common. The usual 4,500 W tank needs 23.4 A, so it goes on 10 AWG copper with a 25 A or 30 A breaker as the nameplate allows. Some provinces have interpretations under Rule 62-114 that differ for small heaters, so check with your inspector.
Level 2 EV chargers and other loads
- 24 A EV charger: EV charging is a continuous load, and Rule 8-104 limits a continuous load to 80% of a standard breaker, so a 24 A (5.8 kW) charger goes on a 30 A circuit with 10 AWG copper.
- RV pedestal (TT-30R): 30 A at 120 V. At 120 V, voltage drop doubles for the same length compared with 240 V, so see the 120 V distance table.
- Air conditioners and heat pumps: size from the nameplate minimum circuit ampacity and maximum overcurrent protection. Motor circuits fall under Section 28, which is one of the exceptions to Rule 14-104(2).
Wire size for 30 amps by distance (metres)
Smallest size that keeps a run at or under the Rule 8-102 3% limit. The 24 A columns use the Rule 8-102 default for an unknown load (80% of a 30 A breaker); the 30 A columns are for a known full load.
120/240 V single phase (dryer, water heater, EV, subpanel)
| Run | Cu, 24 A | Cu, 30 A | Al, 24 A | Al, 30 A |
|---|---|---|---|---|
| 10 m | 10 AWG | 10 AWG | 8 AWG | 8 AWG |
| 15 m | 10 AWG | 10 AWG | 8 AWG | 8 AWG |
| 20 m | 10 AWG | 10 AWG | 8 AWG | 8 AWG |
| 25 m | 10 AWG | 10 AWG | 8 AWG | 8 AWG |
| 30 m | 10 AWG | 10 AWG | 8 AWG | 6 AWG |
| 40 m | 8 AWG | 8 AWG | 6 AWG | 6 AWG |
| 50 m | 8 AWG | 6 AWG | 6 AWG | 4 AWG |
| 60 m | 6 AWG | 6 AWG | 4 AWG | 4 AWG |
| 75 m | 6 AWG | 4 AWG | 4 AWG | 3 AWG |
| 100 m | 4 AWG | 4 AWG | 3 AWG | 2 AWG |
120 V (RV pedestal, 30 A receptacle)
| Run | Cu, 24 A | Cu, 30 A |
|---|---|---|
| 5 m | 10 AWG | 10 AWG |
| 10 m | 10 AWG | 10 AWG |
| 15 m | 10 AWG | 10 AWG |
| 20 m | 8 AWG | 8 AWG |
| 25 m | 8 AWG | 6 AWG |
| 30 m | 6 AWG | 6 AWG |
| 40 m | 6 AWG | 4 AWG |
| 50 m | 4 AWG | 4 AWG |
Example: a 30 A circuit to a detached garage 45 m away, load not yet known. Rule 8-102 says to use 24 A. At 240 V, 10 AWG copper reaches only 37 m, so step up to 8 AWG, which reaches 59 m. The same run at 120 V is much tighter: 10 AWG reaches 18 m and 8 AWG 29 m, so it takes 6 AWG (46 m). The 5% total limit includes the service and any feeder upstream, so leave room for them.
Maximum length at 30 amps by wire size
The longest one-way run, in metres, before each size reaches the drop shown. Three-phase columns use the √3 formula and are resistance-only figures.
Copper
| Size | 120 V, 24 A, 3% | 240 V, 24 A, 3% | 240 V, 30 A, 3% | 240 V, 24 A, 5% | 208 V 3-ph, 24 A, 3% | 600 V 3-ph, 24 A, 3% |
|---|---|---|---|---|---|---|
| 10 AWG | 18 | 37 | 30 | 62 | 37 | 109 |
| 8 AWG | 29 | 59 | 47 | 99 | 59 | 172 |
| 6 AWG | 46 | 93 | 74 | 155 | 93 | 268 |
| 4 AWG | 74 | 148 | 118 | 247 | 148 | 428 |
| 3 AWG | 93 | 186 | 149 | 311 | 186 | 538 |
| 2 AWG | 117 | 235 | 188 | 392 | 235 | 680 |
| 1 AWG | 148 | 296 | 237 | 494 | 297 | 857 |
Aluminum
| Size | 120 V, 24 A, 3% | 240 V, 24 A, 3% | 240 V, 30 A, 3% | 240 V, 24 A, 5% | 208 V 3-ph, 24 A, 3% | 600 V 3-ph, 24 A, 3% |
|---|---|---|---|---|---|---|
| 8 AWG | 18 | 36 | 29 | 60 | 36 | 104 |
| 6 AWG | 28 | 56 | 45 | 94 | 56 | 163 |
| 4 AWG | 45 | 90 | 72 | 150 | 90 | 259 |
| 3 AWG | 56 | 113 | 90 | 189 | 113 | 327 |
| 2 AWG | 71 | 143 | 114 | 238 | 143 | 413 |
| 1 AWG | 90 | 180 | 144 | 301 | 180 | 521 |
| 1/0 AWG | 113 | 227 | 181 | 379 | 227 | 656 |
For your exact load and length, use the Canadian voltage drop calculator or the Canadian wire size calculator, which checks ampacity, Rule 14-104 and Rule 8-102 together.
Bonding conductor for 30 amps
- Bonding conductor (Table 16, Rule 10-616): 12 AWG copper or 10 AWG aluminum for an overcurrent device rated over 20 A up to 30 A.
- Neighbouring rows: devices up to 20 A need 14 AWG copper or 12 AWG aluminum; over 30 A up to 60 A need 10 AWG copper or 8 AWG aluminum.
- NMD90 cable: the bare bonding conductor inside 10/2 and 10/3 cable is already sized for the cable.
- Upsized conductors: if you upsize the circuit conductors for voltage drop, confirm with your inspector whether the bonding conductor must be increased under the edition adopted in your province.
When more than three wires share a raceway
CEC Table 5C multiplies the ampacity by 0.80 for 4 to 6 conductors and 0.70 for 7 to 24. Starting from the 90 °C column of T90 Nylon, 10 AWG copper gives 40 × 0.80 = 32 A, still enough for 30 A. At 7 to 24 conductors it drops to 28 A, so upsize to 8 AWG (55 × 0.70 = 38 A). The final ampacity still can't exceed the termination column. See CEC Table 5C for the full chart and hot-location factors.
How much load can a 30 amp circuit carry?
| System | At 30 A | At 24 A (80%) |
|---|---|---|
| 120 V single phase | 3.6 kW | 2.9 kW |
| 240 V single phase (120/240 V) | 7.2 kW | 5.8 kW |
| 208 V three phase (120/208 V) | 10.8 kW | 8.6 kW |
| 600 V three phase (347/600 V) | 31.2 kW | 24.9 kW |
Balanced load, unity power factor. Rule 8-104 limits a continuous load on a breaker not marked for 100% continuous operation to 80% of its rating. The amps to watts calculator handles power factor.
CEC vs NEC for 30 amps
The answer is the same in both countries: 10 AWG copper, because CEC Rule 14-104(2) and NEC 240.4(D) put the same 30 A cap on 10 AWG copper, and both cap 10 AWG aluminum at 25 A, so 8 AWG aluminum is needed in either country. The differences: voltage drop is mandatory in Canada under Rule 8-102 (3% per circuit, 5% total) instead of an informational note, and the code works in metres. The bonding conductor is smaller in Canada: CEC Table 16 gives 12 AWG copper for a 30 A device, while NEC Table 250.122 gives 10 AWG copper. For the US version with feet, see wire size for 30 amps (NEC). For larger Canadian circuits, see 50 amps, 60 amps, 100 amps and 200 amps.
Sources
- VRI Electrical, Cable Ampacity Tables – CEC / CSA C22.1 (Tables 2, 4 and 5C)
- IAEI Magazine, When is overcurrent protection required? (Rule 14-104(2) limits)
- Régie du bâtiment du Québec, Articles 14-104 et tableau 13
- CSA Group, CEC Section 8 excerpt (Rules 8-102, 8-104)
- Electrical Industry News Week, Guide to the CE Code, Section 62 (Rules 62-114, 62-402)
- Hongbin Li, Bonding conductor size, CSA C22.1:24 Table 16
- Conductor resistance: NEC Chapter 9 Table 8 values at 75 °C, converted to metres