What Size Wire for 30 Amps?

10 AWG copper or 8 AWG aluminum for a 30 A circuit (NEC Table 310.16 and 240.4(D)). Below: why 12 AWG never goes on a 30 A breaker, dryers and 14-30 outlets, water heaters, 24 A EV chargers and 30 A RV hookups, wire size by distance at 120 and 240 V, max length tables, and the ground and conduit size.

Quick answer: wire size for a 30 amp breaker

Minimum conductor allowed on a 30 A breaker, with not more than three current-carrying conductors at 30 °C (86 °F) ambient.

Wire and terminal ratingMinimum sizeTable ampacity
Copper, 60 °C column (NM cable, unmarked terminals)10 AWG30 A
Copper, 75 °C column (THHN/THWN-2, 75 °C terminals)10 AWG35 A
Aluminum, 60 °C column8 AWG35 A
Aluminum, 75 °C column (XHHW-2, 75 °C terminals)8 AWG40 A

Unlike larger circuits, the terminal temperature does not change the answer here: 10 AWG copper is 30 A even in the 60 °C column, so it suits NM cable, UF cable and THHN in conduit alike. Its 75 °C and 90 °C ratings (35 A and 40 A) are only useful as a starting point for derating, because the breaker is still capped at 30 A.

The small-conductor rule: why 12 AWG and 10 AWG aluminum fail

NEC 240.4(D) sets maximum breaker sizes for small wire that override Table 310.16:

WireTable ampacity (60/75/90 °C)Max breaker, 240.4(D)On a 30 A breaker?
14 AWG copper15 / 20 / 25 A15 ANo
12 AWG copper20 / 25 / 30 A20 ANo
10 AWG copper30 / 35 / 40 A30 AYes
12 AWG aluminum15 / 20 / 25 A15 ANo
10 AWG aluminum25 / 30 / 35 A25 ANo
8 AWG aluminum35 / 40 / 45 ANo 240.4(D) limitYes

So 10 AWG copper is the smallest wire allowed on 30 A, and it is also the largest breaker 10 AWG copper can have (outside the motor, A/C and welder exceptions in 240.4(G), where the equipment nameplate sets the maximum breaker).

Wire size for a 30 amp dryer (NEMA 14-30)

NEC 220.54 counts a household electric dryer at 5,000 W or its nameplate rating, whichever is larger. A 5,000 W dryer at 240 V draws 20.8 A, and most dryers list a 30 A circuit on the nameplate. The usual wiring is:

Wire size for a 30 amp water heater

NEC 422.13 treats a fixed storage water heater of 120 gallons or less as a continuous load, so the branch circuit must be at least 125% of the nameplate current. For common 240 V elements:

Element (240 V)Current× 125%BreakerCopper wire
3,500 W14.6 A18.2 A20 A12 AWG
4,500 W18.8 A23.4 A25 A10 AWG
5,500 W22.9 A28.6 A30 A10 AWG

A water heater has no 120 V parts, so 10/2 NM-B with ground is enough. If the nameplate gives a 208 V rating or a different wattage, recalculate from the nameplate. Tankless electric heaters draw far more and often need several 40 A to 60 A circuits.

Wire size for a 24 A EV charger or a 30 amp RV hookup

EV charger: EV supply equipment is a continuous load, so NEC 625.41 sizes the breaker at 125% of the charger's setting. A charger set to 24 A needs a 30 A breaker and 10 AWG copper. A Level 2 charger on a 30 A circuit adds roughly 5.8 kW at 240 V.

RV pedestal: a 30 A RV hookup is 120 V, not 240 V. It uses a NEMA TT-30R receptacle with one hot, a neutral and a ground, wired with 10 AWG copper. Because the voltage is half, voltage drop limits the run sooner: see the 120 V column below.

Air conditioners and heat pumps: use the nameplate minimum circuit ampacity (MCA) for the wire and the maximum overcurrent protection (MOCP) for the breaker, per NEC Article 440. A unit with an MCA of 22 A and an MOCP of 30 A can use 10 AWG copper on a 30 A breaker, and some units allow 12 AWG wire with a larger breaker under 240.4(G).

Wire size for 30 amps by distance

Smallest size that keeps the run at or under a 3% voltage drop. The 24 A columns are for a continuous load on a 30 A breaker, such as an EV charger. Ampacity sets the floor, so the table never goes below 10 AWG copper or 8 AWG aluminum.

One-way run length. 3% drop, NEC Chapter 9 Table 8 resistance at 75 °C.
RunCu, 120 V, 30 ACu, 240 V, 30 ACu, 240 V, 24 AAl, 240 V, 30 AAl, 240 V, 24 A
50 ft8 AWG10 AWG10 AWG8 AWG8 AWG
75 ft8 AWG10 AWG10 AWG8 AWG8 AWG
100 ft6 AWG8 AWG10 AWG6 AWG8 AWG
125 ft4 AWG8 AWG8 AWG6 AWG6 AWG
150 ft4 AWG8 AWG8 AWG4 AWG6 AWG
200 ft3 AWG6 AWG6 AWG4 AWG4 AWG
250 ft2 AWG4 AWG6 AWG3 AWG4 AWG
300 ft2 AWG4 AWG6 AWG2 AWG3 AWG

Example: a 24 A EV charger 125 ft from the panel. 10 AWG copper reaches 123 ft at 24 A, so the run needs 8 AWG copper, which reaches 196 ft. Check that the charger and breaker terminals accept the larger wire, and upsize the ground too (see ground).

Maximum length at 30 amps by wire size

The longest one-way run, in feet, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are DC resistance figures.

Copper

Size120 V, 3%240 V, 3%240 V at 24 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
10 AWG499912316599229
8 AWG78157196261157362
6 AWG122244305407244564
4 AWG194389487649389899
3 AWG2444896128164901131
2 AWG30961877310306191428
1 AWG38977997412987791799

Aluminum

Size120 V, 3%240 V, 3%240 V at 24 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
8 AWG479511915895219
6 AWG74148185247148342
4 AWG118236295393236545
3 AWG148297372496297687
2 AWG188376470626376868
1 AWG2374745927904741095
1/0 AWG2985977469955971378

Formulas: single phase L = %·V·1000 / (2·I·R), three phase L = %·V·1000 / (√3·I·R), with R in ohms per 1000 ft. The NEC informational notes in 210.19 and 215.2 recommend 3% on a branch circuit or feeder and 5% total. Use the voltage drop calculator for your exact load.

Ground wire for 30 amps

Conduit size for 30 amp wire

Smallest conduit at 40% fill (NEC Chapter 9 Table 1) using THHN/THWN-2 areas from Chapter 9 Table 5.

RunConductorsArea, in²EMTPVC 40
Dryer or 14-30 circuit, copper (2 hots + neutral)3 × 10 AWG + 10 AWG0.0841/21/2
Water heater, A/C or 24 A EV charger, copper (2 hots)2 × 10 AWG + 10 AWG0.0631/21/2
Subpanel feeder, aluminum 75 °C (2 hots + neutral)3 × 8 AWG + 8 AWG0.1463/43/4
EV circuit upsized for 125 ft, copper (2 hots)2 × 8 AWG + 8 AWG0.1101/21/2

XHHW-2 aluminum areas differ slightly from THHN, so check the conduit fill calculator for your insulation.

How much load can a 30 amp circuit carry?

SystemAt 30 AContinuous (24 A)
120 V single phase3.6 kW2.9 kW
240 V single phase7.2 kW5.8 kW
208 V three phase10.8 kW8.6 kW
480 V three phase24.9 kW20.0 kW

Balanced load, unity power factor. The amps to watts calculator handles power factor.

When more than three wires share a conduit

With four to six current-carrying conductors in one raceway, NEC 310.15(C)(1) cuts ampacity to 80%. Starting from the 90 °C column, 10 AWG copper gives 32 A, still enough for 30 A. At seven to nine conductors (70%) it drops to 28 A, so upsize to 8 AWG (38 A). See wire derating.

In Canada

CEC Table 2 also rates 10 AWG copper at 30 A in the 60 °C column, and CEC Rule 14-104 limits the overcurrent protection on small conductors in the same way as NEC 240.4(D), so a 30 A circuit is 10 AWG copper in Canada too. Rule 8-102 makes the 3% and 5% voltage drop limits mandatory, and distances are in metres. See CEC Table 2 for run lengths in metres by breaker, or use the Canadian wire size calculator.

For larger circuits, see wire size for 50 amps, 60 amps, 100 amps and 200 amps.

This page is a quick reference. Confirm against the code edition your jurisdiction has adopted, the equipment markings and your inspector.

Frequently asked questions

What size wire for 30 amps?

10 AWG copper or 8 AWG aluminum. 10 AWG copper is 30 A in the 60 °C column of NEC Table 310.16, so it works in NM cable too. Aluminum needs 8 AWG because NEC 240.4(D) caps 10 AWG aluminum at 25 A.

Can I use 12 gauge wire on a 30 amp breaker?

No. NEC 240.4(D) limits 12 AWG copper to a 20 A breaker, whatever its table ampacity. A 30 A breaker on 12 AWG wire is a fire risk because the breaker will let the wire overheat before it trips.

Is 10/2 or 10/3 wire right for 30 amps?

Both are 10 AWG copper rated 30 A as NM-B. Use 10/2 with ground for 240 V-only loads such as a water heater or a hardwired EV charger. Use 10/3 with ground when the load needs a neutral, such as a dryer on a NEMA 14-30 receptacle.

What size wire for a 30 amp dryer?

10/3 NM-B with ground (10 AWG copper) feeding a 4-wire NEMA 14-30 receptacle. NEC 220.54 counts a household dryer at 5,000 W or its nameplate rating, whichever is larger, and most electric dryers list a 30 A circuit.

What size wire for a 30 amp RV hookup?

A 30 A RV pedestal uses a 120 V NEMA TT-30R receptacle with one hot, a neutral and a ground, so 10 AWG copper. At 120 V voltage drop matters more: 10 AWG reaches about 49 ft one way at a full 30 A before passing 3%, so longer runs need 6 AWG copper at 100 ft.

How far can you run 10 AWG wire on a 30 amp circuit?

About 99 ft one way at 240 V and a full 30 A before drop passes 3%, 123 ft at 24 A, or 49 ft at 120 V. These use the NEC Chapter 9 Table 8 resistance for 10 AWG uncoated copper, 1.21 ohms per 1000 ft.

What size ground wire for 30 amps?

10 AWG copper or 8 AWG aluminum, from the 30 A row of NEC Table 250.122. If the hot conductors are upsized for voltage drop, 250.122(B) requires the ground to be upsized by the same circular mil ratio.