What Size Wire for 40 Amps?

8 AWG copper, or 8 AWG aluminum on 75 °C terminals, for a 40 A circuit (NEC Table 310.16 and 240.4(D)). Below: why 10 AWG fails, ranges and cooktops, 32 A EV chargers, A/C units, wire size by distance at 240 V, max length tables, and the ground and conduit size.

Quick answer: wire size for a 40 amp breaker

Minimum conductor allowed on a 40 A breaker, with not more than three current-carrying conductors at 30 °C (86 °F) ambient.

Wire and terminal ratingMinimum sizeTable ampacity
Copper, 60 °C column (NM cable, unmarked terminals)8 AWG40 A
Copper, 75 °C column (THHN/THWN-2, 75 °C terminals)8 AWG50 A
Aluminum, 60 °C column6 AWG40 A
Aluminum, 75 °C column (XHHW-2, 75 °C terminals)8 AWG40 A

For copper the terminal rating does not change the answer: 8 AWG copper is 40 A in the 60 °C column, exactly enough for 40 A, so 8 AWG NM-B cable is allowed. For aluminum it does: 8 AWG aluminum is 35 A at 60 °C and 40 A at 75 °C, so it only works when the conductor and both terminations are rated 75 °C (NEC 110.14(C)). Otherwise use 6 AWG aluminum (40 A at 60 °C).

Why 10 AWG copper is not enough

WireTable ampacity (60/75/90 °C)Max breakerOn a 40 A breaker?
10 AWG copper30 / 35 / 40 A30 A (240.4(D))No
8 AWG copper40 / 50 / 55 ANo 240.4(D) limitYes
10 AWG aluminum25 / 30 / 35 A25 A (240.4(D))No
8 AWG aluminum35 / 40 / 45 A40 A at 75 °CYes, 75 °C only
6 AWG aluminum40 / 50 / 55 ANo 240.4(D) limitYes

10 AWG copper has a 75 °C ampacity of 35 A, but 240.4(D) still limits it to a 30 A breaker. 8 AWG copper on a 40 A breaker is also the natural maximum for NM cable: 40 A is a standard breaker size under 240.6(A), and 8 AWG NM-B is rated exactly 40 A.

Wire size for a 40 amp range, cooktop or wall oven

Wire size for a 32 amp EV charger

EV supply equipment is a continuous load, so NEC 625.41 sizes the breaker at 125% of the charger's setting. A charger set to 32 A needs a 40 A breaker and 8 AWG copper. Common settings:

Charger settingPower at 240 V× 125%BreakerCopper wire (short run)
16 A3.8 kW20 A20 A12 AWG
24 A5.8 kW30 A30 A10 AWG
32 A7.7 kW40 A40 A8 AWG
40 A9.6 kW50 A50 A6 AWG
48 A11.5 kW60 A60 A6 AWG

A 32 A charger adds about 7.7 kW. If the charger plugs into a NEMA 14-50 receptacle, the receptacle needs a 50 A circuit even when the charger is set to 32 A, so the wire becomes 6 AWG copper. A hardwired charger set to 32 A can stay on 40 A.

A/C, heat pumps and other 40 amp loads

For air conditioners and heat pumps, use the nameplate minimum circuit ampacity (MCA) for the wire and the maximum overcurrent protection (MOCP) for the breaker (NEC Article 440). A unit with an MCA of 28 A and an MOCP of 40 A can use 10 AWG copper on a 40 A breaker, because 240.4(G) lets motor and A/C circuits follow the nameplate. A general-purpose circuit, a subpanel or a receptacle cannot.

Other common 40 A loads include electric tankless water heaters (often several 40 A circuits, one per element), hot tub heaters and small subpanel feeders. Storage and tankless water heaters of 120 gallons or less are continuous loads under 422.13, so check the nameplate current times 125%.

Wire size for 40 amps by distance

Smallest size that keeps the run at or under a 3% voltage drop at 240 V. The 32 A columns are for a continuous load on a 40 A breaker, such as an EV charger. Ampacity sets the floor, so the table never goes below 8 AWG.

One-way run length. 3% drop at 240 V, NEC Chapter 9 Table 8 resistance at 75 °C. Aluminum assumes 75 °C terminals.
RunCu, 40 ACu, 32 AAl, 40 AAl, 32 A
50 ft8 AWG8 AWG8 AWG8 AWG
75 ft8 AWG8 AWG6 AWG8 AWG
100 ft8 AWG8 AWG6 AWG6 AWG
125 ft6 AWG8 AWG4 AWG6 AWG
150 ft6 AWG6 AWG4 AWG4 AWG
200 ft4 AWG6 AWG3 AWG4 AWG
250 ft4 AWG4 AWG2 AWG3 AWG
300 ft3 AWG4 AWG1 AWG2 AWG

Example: a 32 A EV charger 150 ft from the panel. 8 AWG copper reaches 147 ft at 32 A, so the run needs 6 AWG copper, which reaches 229 ft. Check that the charger and breaker terminals accept the larger wire, and upsize the ground too (see ground).

Maximum length at 40 amps by wire size

The longest one-way run, in feet, before each size reaches the drop shown. Three-phase columns use the √3 formula. These are DC resistance figures.

Copper

Size120 V, 3%240 V, 3%240 V at 32 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
8 AWG58117147196117272
6 AWG91183229305183423
4 AWG146292365487292674
3 AWG183367459612367848
2 AWG2314635797734641071
1 AWG2925847309745841349
1/0 AWG36873792212297381703

Aluminum

Size120 V, 3%240 V, 3%240 V at 32 A, 3%240 V, 5%208 V 3-ph, 3%480 V 3-ph, 3%
8 AWG35718911971164
6 AWG55111139185111257
4 AWG88177221295177409
3 AWG111223279372223515
2 AWG141282352470282651
1 AWG177355444592355821
1/0 AWG2234475597464481034
2/0 AWG2835667079435661307

Formulas: single phase L = %·V·1000 / (2·I·R), three phase L = %·V·1000 / (√3·I·R), with R in ohms per 1000 ft. The NEC informational notes in 210.19 and 215.2 recommend 3% on a branch circuit or feeder and 5% total. Use the voltage drop calculator for your exact load.

Ground wire for 40 amps

Conduit size for 40 amp wire

Smallest conduit at 40% fill (NEC Chapter 9 Table 1) using THHN/THWN-2 areas from Chapter 9 Table 5.

RunConductorsArea, in²EMTPVC 40
Range or cooktop, copper (2 hots + neutral)3 × 8 AWG + 10 AWG0.1313/43/4
32 A EV charger or A/C, copper (2 hots)2 × 8 AWG + 10 AWG0.0941/21/2
Subpanel feeder, aluminum 75 °C (2 hots + neutral)3 × 8 AWG + 8 AWG0.1463/43/4
EV circuit upsized for 150 ft, copper (2 hots)2 × 6 AWG + 8 AWG0.1383/43/4

XHHW-2 aluminum areas differ slightly from THHN, so check the conduit fill calculator for your insulation.

How much load can a 40 amp circuit carry?

SystemAt 40 AContinuous (32 A)
120 V single phase4.8 kW3.8 kW
240 V single phase9.6 kW7.7 kW
208 V three phase14.4 kW11.5 kW
480 V three phase33.3 kW26.6 kW

Balanced load, unity power factor. The amps to watts calculator handles power factor.

When more than three wires share a conduit

With four to six current-carrying conductors in one raceway, NEC 310.15(C)(1) cuts ampacity to 80%. Starting from the 90 °C column, 8 AWG copper gives 44 A, still enough for 40 A. At seven to nine conductors (70%) it drops to 38 A, so upsize to 6 AWG (52 A). See wire derating.

In Canada

CEC Table 2 also rates 8 AWG copper at 40 A in the 60 °C column, so a 40 A circuit is 8 AWG copper in Canada too, and CEC Rule 14-104 caps 10 AWG copper at 30 A in the same way as NEC 240.4(D). Rule 8-102 makes the 3% and 5% voltage drop limits mandatory, and distances are in metres. See CEC Table 2 for run lengths in metres by breaker, or use the Canadian wire size calculator.

For a smaller circuit, see wire size for 30 amps. For larger circuits, see 50 amps, 60 amps, 100 amps and 200 amps.

This page is a quick reference. Confirm against the code edition your jurisdiction has adopted, the equipment markings and your inspector.

Frequently asked questions

What size wire for 40 amps?

8 AWG copper, or 8 AWG aluminum with 75 °C terminals (6 AWG aluminum in the 60 °C column). 8 AWG copper is rated 40 A even in the 60 °C column of NEC Table 310.16, so 8 AWG NM-B works on a 40 A breaker.

Can I use 10 gauge wire on a 40 amp breaker?

No, not for a general circuit. NEC 240.4(D) caps 10 AWG copper at a 30 A breaker. The only exceptions are equipment whose nameplate lists a larger maximum breaker, such as air conditioners and motors under 240.4(G) and Article 440, where the wire follows the minimum circuit ampacity.

Is 8/2 or 8/3 wire right for 40 amps?

Both are 8 AWG copper rated 40 A as NM-B. Use 8/2 with ground for 240 V-only loads such as a hardwired EV charger, A/C condenser or tankless water heater element. Use 8/3 with ground when the load needs a neutral, such as a range, cooktop or wall oven with 120 V controls.

What size wire for a 40 amp range?

8/3 copper with ground on a 40 A breaker. NEC 210.19(A)(3) requires at least a 40 A branch circuit for a household range rated 8¾ kW or more. Many larger ranges list a 50 A circuit on the nameplate, which needs 6 AWG copper, so always follow the nameplate.

What size breaker and wire for a 32 amp EV charger?

A 40 A breaker and 8 AWG copper. NEC 625.41 sizes the breaker at 125% of the charger's continuous rating, and 32 A × 1.25 = 40 A. Over about 147 ft one way, upsize to 6 AWG copper to stay under 3% drop.

How far can you run 8 AWG wire on a 40 amp circuit?

About 117 ft one way at 240 V and a full 40 A before drop passes 3%, 147 ft at 32 A, or 58 ft at 120 V. These use the NEC Chapter 9 Table 8 resistance for 8 AWG uncoated copper, 0.764 ohms per 1000 ft.

What size ground wire for 40 amps?

10 AWG copper or 8 AWG aluminum, from the 60 A row of NEC Table 250.122, which covers breakers above 20 A up to 60 A. If the hot conductors are upsized for voltage drop, 250.122(B) requires the ground to be upsized by the same circular mil ratio.